3 – 2
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Section 3
•
Hardware Architecture
Digital Input/Output (I/O)
Refer to Table 3-1.
Compressor Start Output:
• When the Vission 20/20 signals the compressor to
start, this output is energized. When the Vission
20/20 signals the compressor to stop, this output is
de-energized.
Oil Pump Start Output:
• When the Vission 20/20 signals the oil pump to start,
this output is energized. When the Vission 20/20 sig-
nals the oil pump to stop, this output is de-energized.
Capacity Increase Output:
• This output is only active when the compressor is
running. When the Vission 20/20 determines that
the compressor should increase capacity by moving
the slide valve to a higher percentage, this output is
energized. Once the slide valve reaches 100%, this
output will not energize.
Capacity Decrease Output:
• This output is only active when the compressor is
running. When the Vission 20/20 determines that
the compressor should decrease capacity by moving
the slide valve to a lower percentage, this output is
energized. Once the slide valve reaches 0%, this out-
put will not energize.
Volume Increase Output:
• This output is only active when the compressor is
running. When the Vission 20/20 determines that
the compressor should increase Volume Index (VI) by
moving the volume slide to a higher percentage, this
output is energized. Once the volume slide reaches
100%, this output will not energize.
Volume Decrease Output:
• This output is only active when the compressor is run-
ning. When the Vission 20/20 determines that the
compressor should decrease Volume Index (VI) by
moving the volume slide to a lower percentage, this
output is energized. Once the volume slide reaches
0%, this output will not energize.
Oil Sump Heater Output:
• This output is active and energized when the oil
separator temperature is lower than the oil separator
temperature setpoint. It is de-energized when the oil
separator temperature is higher than the oil separa-
tor temperature setpoint.
Trip Output:
• This output is energized when the system has no
Trips. If a trip is issued, the output de-energizes and
stays de-energized until the trip condition is cleared.
Slide Valve Setpoint #1 Output (Economizer Port #1):
• Normally used for an economizer solenoid, but could
be used for other devices. When the compressor slide
valve percentage is equal to or greater than “slide
valve set-point #1”, the output is energized. When
the compressor slide valve percentage is less than
“slide valve set-point #1”, the output is de-energized.
Slide Valve Setpoint #2 Output (Hot Gas Bypass):
• Normally used for a hot gas solenoid, but could be
used for other devices. When the compressor slide
valve percentage is equal to or greater than “slide
valve set-point #2”, the output is energized. When
the compressor slide valve percentage is less than
“slide valve set-point #2”, the output is de-energized.
Alarm Output:
• This output is energized when the system has no
alarms. If an alarm is issued, the output de-energizes
and stays de-energized until the alarm condition is
cleared.
Economizer Port #2 Output:
• This output is energized when the compressor slide
valve percentage is equal to or greater than slide
valve set-point for economizer port 2. It is de-ener-
gized when the compressor slide valve percentage is
less than slide valve set-point for economizer port 2.
Liquid Injection #1 Output:
• The function of this output will differ depending on
what type liquid injection is selected. If the liquid in-
jection solenoid only is chosen, then the output will
energize when discharge temperature is above liquid
injection setpoint #1 and the oil separator tempera-
ture is above the oil separator temperature override
set-point. The output is de-energized when any one
of the above condition is not met.
• If the compressor has liquid injection with motor-
ized value oil cooling, then this output is energized
when the compressor is running and the discharge
temperature is above the oil separator temperature
override set-point and the oil separator temperature
is above the override setpoint. The output is de-en-
ergized when the discharge temperature falls below
the “on” setpoint minus the solenoid differential or
when oil separator temperature is below the oil sepa-
rator temperature override set-point.
Liquid Injection #2 Output:
• Not De
fi
ned
Summary of Contents for Vission 20/20
Page 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Page 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 257: ......