3 – 7
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Section 3
•
Hardware Architecture
Table 3-3. Analog Outputs
Board
I/O #
Description
Type
10
1
Compressor VFD
4-20 mA
10
2
Condenser / Remote Oil Cooler VFD
4-20 mA
10
3
% Slide Valve Position
4-20 mA
10
4
Motorized Valve (Cool Compression or Liquid
Injection), V+
4-20 mA
10
5
Auxiliary Output #1
4-20 mA
10
6
Auxiliary Output #2
4-20 mA
10
7
Auxiliary Output #3
4-20 mA
10
8
Auxiliary Output #4
4-20 mA
Figure 3-2. Digital I/O Board Layout
Board
I/O #
Description
Type
9
28
Auxiliary #12
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD
9
29
Auxiliary #13
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD
9
30
Auxiliary #14
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD
9
31
Auxiliary #15
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD
9
32
Auxiliary #16
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD
Table 3-2. Analog Inputs (2 of 2)
Digital & Analog I/O Boards Layout
It is important to install the boards in the proper layout.
For the correct digital and analog input/output (I/O)
board layout, see Figure 3-2.
Dipswitches
• Each board has a dipswitch which sets its communi-
cations address so that it can communicate with the
CPU board. The dipswitch settings must be correct
or the I/O will not function.
Jumpers
• Jumpers are required on the analog boards to con-
fi
gure them for the type of sensors used. The jumper
table for the analog board shows the optional jump-
er con
fi
gurations for sensors other than the default
Vilter standard. If a different sensor is to be used, the
jumpers on the analog board need to be changed. In
addition, the con
fi
guration for this sensor must be
changed in the Instrument Calibration screen. The
following illustrations show the Vilter default con-
fi
gurations for the Vission 20/20.
Summary of Contents for Vission 20/20
Page 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Page 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 257: ......