12 – 1
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Section 12
•
Service Options
Overview
The Service Option screen allows the operator the ability
to force individual digital or analog outputs ON. This fea-
ture is used for diagnostic purposes during initial setup
and/or if the operator suspects an issue with the out-
puts. The buttons in this screen are not available while
the compressor is running .
Digital Outputs
The digital output buttons are momentary toggle but-
tons. The output will be active while the operator has his
fi
nger on the button. The output will deactivate when
the operators
fi
nger is removed. The operator can mea-
sure the output at the terminal block or view the output
by watching the LEDs located on the cards. For Digital
Output screens, see Figures 12-1, 12-2, 12-3 and 12-4.
Reference Figure 12-1.
Compressor Start:
• Activates the output assigned to the compressor mo-
tor starter. The output is connected to terminal 11
and is the 1st LED on card 1.
Oil Pump Start:
• Activates the output assigned to the oil pump. The
output is connected to terminal 12 and is the 2nd
LED down on card 1.
Capacity Increase Motor:
• Activates the output assigned to the increase input
of the capacity actuator. The output is connected to
terminal 13 and is the 3rd LED down on card 1.
Capacity Decrease Motor:
• Activates the output assigned to the decrease input
of the capacity actuator. The output is connected to
terminal 14 and is the 4th LED down on card 1.
Figure 12-1. Service Options Screen - Digital Outputs (Page 1)
Summary of Contents for Vission 20/20
Page 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Page 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 257: ......