Section 18
•
Auxiliary Input / Output
Overview
The Auxiliary Input/Output (I/O) section of the Vission
20/20 gives the operator
fl
exibility to add peripheral
instruments and/or devices such as motors, valves and
solenoids. With these additions, customer con
fi
gurable
I/Os are useful in expanding the functions of the Vission
20/20 where it was not explicitly designed to control.
Setting up one or more of the auxiliary inputs or out-
puts start with the con
fi
guration screen. In order to en-
able the auxiliary I/O, the Vission 20/20 must
fi
rst be
equipped with one of the available expandable I/O cards
and the card must be selected on page 6 of the con
fi
gu-
ration screen. Once the appropriate card is available,
then the operator will be permitted to enable and name
the desired auxiliary I/O. The operator can then navigate
to the Auxiliary I/O screen where the operator can de
fi
ne
how that I/O will operate.
Digital Inputs
The Digital Inputs section of the auxiliary I/O allows
an operator to con
fi
gure the auxiliary digital inputs,
see Figure 18-1. The digital input can be con
fi
gured to
produce an alarm, a trip, and an inhibit on either a high
or low input. A low input is 0vac and a high is 120vac on
the enabled input. Leaving all options in their default set-
ting will mean no action will be taken on an enable input.
The input will simply be available for viewing at the panel
or by communications.
Trip/Alarm Check:
• Selecting this checkbox enables the alarms and/or
trip functions of the Vission 20/20 for the desired
digital input. The accompanying drop-down box
gives the operator the
fl
exibility to choose whether
the alarm and/or tip occurs if the input is high or low.
Inhibit Check:
• Selecting this checkbox enables the inhibit function
of the Vission 20/20 for the desired digital input. An
inhibit check prevents the compressor from starting
if the condition is true where a trip will shut down
the compressor after it as started. The inhibit can be
selected to inhibit on a high or low input and can be
selected to work with or without the alarm and trip
function
Figure 18-1. Auxiliary I/O Screen - Digital Inputs (Page 1)
Summary of Contents for Vission 20/20
Page 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Page 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 257: ......