background image

TEST

Tri-Color LED

Fault/Status Indicator

Count Button

Hardstart

Option

Fan

Common

Compressor/Fan

Capacitor Outputs

Short Cycle

Protection

Delay

Dipswitch

Brownout

 Protection

Brown

Dipswitch

C

Y

Thermostat

Input

Test

Button

Crankcase Heater

Power

Line

Inputs

L

1

L

2

Run

Common

Delay

Brown

ON

COUNT

Compressor

Outputs

MOUNTING 

QUICK REFERENCE 

 

1. 

Disconnect power to the condensing unit or heat pump at the 
disconnect switch and/or main electrical panel. Ensure that all 
sources of power are disconnected before proceeding.

2. 

Label wires and remove old contactor.

3. 

Find a suitable mounting location inside the control box. Rotate 

SureSwitch as necessary to allow space for wiring and other 
components.

4. 

Loosen four housing captive screws attaching the bottom 

mounting plate to the main housing and separate the mounting 
plate from the main housing.

5. 

The bottom of the mounting plate has four mounting holes that 
match the typical mounting screw locations of a single or two-pole 
contactor. Secure the bottom mounting plate to the control box 
using the two self-tapping screws provided.

6. 

Replace the main housing on the mounting plate and secure by 

tightening all four housing captive screws. Take care to avoid over 
tightening.

7. 

Connect line and control voltage wiring. Refer to the wiring 

diagrams provided for more information. Tighten the 

L

1

,

 L

2

R

 and 

C

 lugs to the recommended torque specifications. 

8. 

Affix the provided Quick Reference Label inside the control box for 

future service.

CONTROL 

CIRCUIT

L

2

L

1

Run
Common

LOAD

LINE

C

Y

Figure 

1

 - Two Piece Design

Figure 

3

 - Electrical Diagram

MAIN HOUSING

Housing
Screws

Mounting

Holes

MOUNTING PLATE

SPECIFICATIONS 

 

ELECTRICAL RATINGS

Line Voltage Input

 ...........................................

240 VAC, 50/60 Hz

Full Load Amperes (FLA)

 .................................

40 A

Locked Rotor Amperes (LRA)

 ..........................

200A

Control (Coil) Voltage (Y, C)

 .............................

24 VAC, 50/60 Hz

 

RECOMMENDED TERMINAL TORQUE – L

1

, L

2

, R and C

#4

 – 6 AWG .....................................................

45

 in-lbs

#8

 AWG ..........................................................

40

 in-lbs

#10

 – 

14

 AWG .................................................

35

 in-lbs

Figure 

2

 - 

49

P

11

-

843

 Terminals and Switches

Summary of Contents for White Rogers SureSwitch 49P11-843

Page 1: ...on should be done by a qualified heating and air conditioning contractor or licensed electrician Do not exceed the specification ratings All wiring must conform to local and national electrical codes and ordinances This control is a precision instrument and should be handled carefully Rough handling or distorting components could cause the control to malfunction Following installation or replaceme...

Page 2: ...ng plate has four mounting holes that match the typical mounting screw locations of a single or two pole contactor Secure the bottom mounting plate to the control box using the two self tapping screws provided 6 Replace the main housing on the mounting plate and secure by tightening all four housing captive screws Take care to avoid over tightening 7 Connect line and control voltage wiring Refer t...

Page 3: ...e disabled by setting the Delay dipswitch to the OFF position LINE VOLTAGE BROWNOUT PROTECTION Brownout protection will de energize the compressor and fan if line voltage drops below 180 VAC for more than four seconds during a call for compressor operation Compressor operation will not resume until line voltage returns to a minimum of 190VAC In addition SureSwitch will not attempt to start the com...

Page 4: ...rankcase Heater 2Wire Hardstart Kit optional FAN HERM COM Line voltage Low voltage Line voltage optional circuit Optional components Legend T1 Fan Run T2 Start Separate Capacitor Optional Fan Capacitor Fan Run Common Start Fan Separate Capacitor Optional Capacitor 49P11 843 SureSwitch 4 Wire Condenser Fans 3 Wire Condenser Fans The following wiring diagram is meant to represent typical installatio...

Page 5: ...on ou par un électricien agréé N excédez pas les spécifications du produit Tout le câblage doit respecter les codes et règlements locaux et nationaux de l électricité Ce thermostat est un instrument de précision et il doit être manipulé avec soin Une manipulation robuste ou la modification des composantes peuvent causer la défaillance du thermostat Après l installation ou le remplacement respectez...

Page 6: ...laque de montage du boîtier principal 5 Le bas de la plaque de montage est pourvu de quatre trous de montage qui correspondent à l emplacement typique des vis de montage pour un contacteur mono ou bipolaire Fixer le bas de la plaque de montage sur la boîte des commandes à l aide des deux vis autotaraudeuses fournies 6 Replacer le boîtier principal sur la plaque de montage et fixer le tout en serra...

Page 7: ...baisse de tension coupe le compresseur et le ventilateur lorsque la tension de ligne chute sous 180V c a pendant plus de quatre secondes alors que le système appelle au fonctionnement du compresseur Le compresseur ne redémarre pas tant que la tension n atteint pas au minimum 190V c a De plus le module SureSwitch ne tente pas de redémarrer le compresseur tant que la tension de ligne est inférieure ...

Page 8: ...cultatives Légende T1 Ventilateur Marche T2 Démarrage Condensateur du ventilateur Ventilateur Marche Neutre Démarrage Condensateur distinct facultatif 49P11 843 SureSwitch Ven lateurs de condensateur à 4 fils Ven lateurs de condensateur à 3 fils Condensateur du ventilateur Condensateur distinct facultatif Condensateur du ventilateur Condensateur distinct facultatif Condensateur du ventilateur Cond...

Page 9: ...cionado o por un electricista profesional No exceda los valores nominales especificados Todas las conexiones eléctricas deben cumplir con los códigos y reglamentaciones locales y nacionales Este control es un instrumento de precisión y debe manipularse con cuidado La manipulación descuidada o la distorsión de los componentes podrían hacer que el control no funcionara correctamente Una vez finaliza...

Page 10: ...taje tiene cuatro orificios de montaje que coinciden con las ubicaciones típicas de los tornillos de montaje de un contactor monopolar o bipolar Fije la placa de montaje inferior a la caja de control utilizando los dos tornillos autorroscantes suministrados 6 Vuelva a colocar la carcasa principal sobre la placa de montaje y fíjela ajustando los cuatro tornillos cautivos de la carcasa Evite ajustar...

Page 11: ...ONTRA CAÍDA DEVOLTAJE DE LÍNEA La protección contra caídas de voltaje desenergiza el compresor y el ventilador si el voltaje de línea cae por debajo de los 180VCA durante más de cuatro segundos durante una llamada de funcionamiento de compresor El funcionamiento del compresor no se reanudará hasta que el voltaje de línea vuelva a 190VCA como mínimo Además SureSwitch no intentará iniciar el compres...

Page 12: ...ERM COM Voltaje de línea Bajo voltaje Circuito opcional de voltaje de línea Componentes opcionales Leyenda T1 Ventilador T2 Arranque Capacitor del ventilador Ventilador Común Arranque Capacitor separado opcional 49P11 843 SureSwitch Ven ladores de condensador de 4 cables Ven ladores de condensador de 3 cables Capacitor del ventilador Funcio namiento Capacitor separado opcional Funcio namiento El s...

Reviews: