background image

1592019030 XEV02D GB r1.2 04.06.2015 

XEV02D 

3/4 

dCt 

Cooling time for DG compressor after DLT alarm: 

0 to 255 min 

dLn 

Number  of  DLT  alarms  in  dLi  hours  before  blocking  compressor: 

0  to  15, 

0=function disabled. 

dLi 

Time  interval  (in  hours)  in  which  to  check  dLn  number  of  DLT  alarms:

  0  to  24 

hours; 0=function disabled. 

CEd 

Maximum compressor capacity (in percentage) in case of probe error:

 0 to 100% 

Cdd 

Maximum compressor capacity (in percentage) in case of DLT alarm and for time 
dLd:

 0 to 100% 

CEi 

Maximum compressor capacity (in percentage) in case of regulation input error:

 

0 to 100% 

dEr 

Alarm delay in case of regulation input/probes reading error:

 0 to 999 sec 

OTHER 

A2F 

ALARM key timed function configuration (push button timed, 3 sec): nu

=not used; 

onF=ON-OFF function.

 

Adr 

Serial address: 

1 to 247 

bAU 

Baudrate for serial communication:

 

9.6

=9600 baud; 

19.2

=19200 buad. 

dP1 

Analogue output value (read only) 

dP2 

Probe P2 value (read only) 

d1S 

Digital input status display (isolated contact) (read only) 

d2S 

Digital input status display (not isolated contact) (read only) 

rEL 

Release Firmware (read only) 

Ptb 

Parameters table code (read only) 

Pr2 

Protected parameters menu access 

8. DIGITAL INPUTS

The device is provided with two digital inputs. One is free of voltage and the other is at high voltage 
and both can be configured as cooling call. In this way the cooling signal can come from instruments 
with direct load outputs or via instruments with output without voltage.

 

9. ELECTRICAL CONNECTIONS

The instrument is provided with pluggable screw terminal block to connect cables with a cross section 
up to 2.5 mm

2

. Heat-resistant cables have to be used. Before connecting cables make sure the power 

supply complies with the instrument’s requirements. Separate the probe cables from the power supply 
cables, from the outputs and the power connections. Do not exceed the maximum current allowed on 
each relay, in case of heavier loads use a suitable external relay. 

10. RS485 SERIAL LINE

All  models  can  be  connected  to  a  MODBUS  network  by  using  the  2-wire  RS485  port.  The  XWEB 
related library and the MODBUS protocol can be issued on customer request from DIXELL. 

11. USE THE HOT-KEY

11.1

 

PROGRAM A HOT-KEY FROM THE INSTRUMENT (UPLOAD) 

1)

Program one controller with the front keypad.

2)

When  the  controller  is  ON,  insert  the 

HOT-KEY

  and  push 

UP

  button;  the  “

uPL

 

message 

appears followed a by flashing “

End

.

 

3)

Push 

SET

 button and the “

End

” will stop flashing.

4)

Turn OFF the instrument, remove the 

HOT-KEY

 and

 

then turn it ON again.

NOTE

: the “

Err

” message is displayed in case of any failed programming operation. In this case, push 

again 

UP 

button  if  you  want  to  restart  the  upload  again  or  remove  the 

HOT-KEY

  to  abort  the 

operation. 

11.2

 

PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

1)

Turn OFF the instrument.

2)

Insert a pre-programmed 

HOT-KEY

 into the 5-PIN connector and then turn the Controller ON.

3)

Automatically  the  parameter  list  present  into  the 

HOT-KEY

  will  be  downloaded  into  the 

Controller memory. The “

doL

” message will blink during this operation, followed a by a flashing 

End

” label. 

4)

After 10 seconds the instrument will restart working with the new parameters.

5)

Remove the 

HOT-KEY

.

NOTE: 

the “

Err

” message is displayed in case of any failed programming operation. In this case, push 

again 

UP 

button  if  you  want  to  restart  the  upload  again  or  remove  the 

HOT-KEY

  to  abort  the 

operation. 

12. ALARM MENU

Press the 

ALARM

 button to access the alarms database menu if. This menu contains a 

LIFO 

format 

log of the last 10 registered alarms. The menu structure is as follows:  
-

the  alarm  number  in  AL0...AL9  format  (0  is  the  oldest  alarm,  9  is  the  last  received  alarm)  is 
displayed once accessed; 

-

it is possible to scroll the registered alarms by using the 

UP

 and 

DOWN

 buttons;

-

it is possible to display the following alarm information (in sequence) by using the 

SET

 button:

the  alarm code (3 digit label according to that described) and alarm duration in 

h.mm

 (1 minutes 

resolution, max stored value is 19h59min). 

12.1

 

ALARMS ARCHIVE ERASING:  

All  saved  alarms  can  be  deleted  by  keeping  the 

ALARM+SET

  key  pressed  for  5  sec  when  into 

ALARM MENU. The display will show the “rSt” label (flashing) for 3 sec and then the default display 
visualization will be restored (

Lod

 variable). 

NOTE:

  

-

All saved alarms can be also deleted via special MODBUS command.

13. DISPLAY MESSAGES

Mess. 

Cause 

Outputs 

A02 

Digital input configured as 

EAL

 function is active  Unchanged 

A03 

Missing  regulating  signal  (analogue  input  drops 
below 

dSL

 value) 

Unchanged 

E01 

DLT alarm active 

Output disabled, alarm output activated 

E02 

dLn 

number  of  DLT  alarms  in  time  interval  (in 

hours) 

dLi

 was detected. 

Output disabled, alarm output activated 

E03 

Digital input configured as 

bAL

 function is active  Output disabled, alarm output activated 

E05 

Missing  regulating  signal  (analogue  input  drops 
below 

dSL

 value more than 

dEr 

time) 

Output disabled, alarm output activated 

E07 

Low temperature alarm active 

Output disabled, alarm output activated 

P1 

Analogue input error 

Output disabled, alarm output activated 

P2 

Temperature transducer in error 

Output disabled, alarm output activated 

13.1

 

ALARM RECOVERY  

Probe alarms “

P1

” and “

P2

” start 

dEr

 seconds after the fault in the read value; they automatically stop 

few seconds after the probe restarts normal operation. Check connections before replacing the probe. 
Alarms 

E01, E03

 and 

E05

 automatically stop as soon as their root causes disappear. 

Alarm 

E02 

and 

E07

 require a manual re-start by switchinf OFF and ON the device or by sending a 

MODBUS command. 

14. TECHNICAL DATA 

Housing: 

self extinguishing ABS

 

Case: 

4 DIN modules 70x135mm with male and female connectors; depth 60mm

 

Mounting: 

DIN RAIL mounted in an omega (3) din rail 

Protection:

 IP20 

Connections: 

screw terminal block 

 2.5 mm

2

 wiring 

Power supply:

 24Vac/dc ±10%; 110VAC ±10% or 230VAC ±10% 

Power absorption: depending on connected valve 

20VA max 

Display:

 3.5 digits with icons, red LEDs, height 14.2 mm 

Temperature input:

   1 temperature probe  

PT1000 probe: 

-55 to 200°C (-67 to 392°F) 

NTC10k probe: 

-40 to 110°C (-40 to 230°F) 

NTC86k probe: 

-40 to 180°C (-40 to 356°F) 

Analogue control input:

 

0 to 10Vdc 
4 to 20mA 

Digital inputs:  

1

 

free of voltage 

1 isolated (voltage depending on the power supply) 

Digital outputs: 

1 relay output, 8(3)A, 250VAC 
1 open collector output, max current 40mA 

TRIAC output: 

max 30W 

Data storage:

 on the non-volatile memory (EEPROM) 

Kind of action: 

1B 

Pollution degree: 

normal 

Software Class:

 A

 

Operating temperature: 

0 to 55°C (32 to 131°F) 

Storage temperature: 

-25 to 60°C (-13 to 140°F)  

Relative humidity:

 20 to 85% (no condensing) 

Resolution: 

 0.1°C or 1°F 

Precision a 25°C (77°F):

 ±0.7°C ±1digit 

15. STANDARD VALUES

Label 

Description 

Range 

Default 

Level 

oA1 

Digital output 1 configuration

 

nu; ALr; CPR; dmd 

CPr 

Pr1 

oA2 

Digital output 2 (o.c.) configuration 

nu, ALr 

nu 

Pr2 

oP1 

Digital output 1 polarity

 

oP; CL 

oP 

Pr1 

oP2 

Digital output 2 (o.c.) polarity

 

oP; CL 

oP 

Pr2 

tbA 

Alarm output deactivation 

no; Yes 

no 

Pr2 

bEn 

Buzzer (software) management 

on; oFF 

on 

Pr2 

P2C 

Temperature  probe  configuration  (it 

depends on the hardware) 

nu; Pt1; ntC; n86  

(*) 

Pr1 

o2 

Probe P2 calibration

 

-12 to 12°C; -21 to 21°F

0.0 

Pr1 

PA4 

Analogue input at 4mA or 0V 

0 to 100% 

0.0 

Pr2 

P20 

Analogue input at 20mA or 10V 

0 to 100% 

100 

Pr2 

Lod 

Default displayed variable

 

PEr; Ain; P2 

PEr 

Pr1 

CF 

Units 

of 

measurement 

for 

temperature

 

°C; °F 

°C 

Pr1 

rES 

Temperature resolution (valid only if 

CF=°C)

 

in; dE 

dE 

Pr1 

i1F 

Digital input 1 configuration (voltage 

free contact)

 

nP; EAL; bAL; onF 

EAL 

Pr1 

i2F 

Digital  input  2  configuration  (high 

voltage input)

 

nP; EAL; bAL; onF 

onF 

Pr1 

i1P 

Digital input 1 polarity

 

oP; CL 

CL 

Pr1 

i2P 

Digital input 2 polarity

 

oP; CL 

CL 

Pr1 

Sut 

Start  up  time:  valve  activation  time 

before starting the regulation 

0.0 to 25.5 sec 

3.0 

Pr1 

tdG 

Modulation time interval

 

6 to 40 sec

 

20 

Pr1 

ALL 

Low temperature alarm

 

-30 to 200°C; 

-22 to 392°F

-30

Pr2 

dLL 

Low  temperature  alarm  activation 

delay

 

0 to 999 sec

 

180 

Pr2 

dLt 

Discharge line temperature

 

-30 to 200°C; 

-22 to 392°F

145 

Pr1 

dth 

Differential

 

0 to 99.9°C;  

0 to 999°F

 

10 

Pr1 

dLd 

DLT alarm activation delay

 

0 to 999 sec

 

60 

Pr1 

dCt 

Cooling  time  for  DG  compressor 

after DLT alarm

 

0 to 255 min

 

10 

Pr1 

Summary of Contents for XEV02D

Page 1: ...LARM CONTROL TRIP DLT alarm is generated when DLT probe P2 temperature is T dLt Until alarm delay time dLd is active the total compressor capacity will be limited to Cdd If alarm delay time dLd is disabled or elapsed General alarm LED and digital output set as alarm oAx ALr is activated If a digital output is set as compressor output oA1 CPr this is also deactivated If a digital output is set as d...

Page 2: ...essed for 3 sec 2 The instruments will show the first parameter present in the Pr1 menu 6 4 ACCESS TO PR2 PARAMETER MENU To access to Pr2 menu 1 Enter the Pr1 menu 2 Select Pr2 parameter and press SET 3 The PAS label will be shown then 0 with 0 blinking Insert 321 password through UP and DOWN buttons then press SET to confirm 6 5 CHANGE A PARAMETERS VALUE To change any parameter value follow this ...

Page 3: ...on max stored value is 19h59min 12 1 ALARMS ARCHIVE ERASING All saved alarms can be deleted by keeping the ALARM SET key pressed for 5 sec when into ALARM MENU The display will show the rSt label flashing for 3 sec and then the default display visualization will be restored Lod variable NOTE All saved alarms can be also deleted via special MODBUS command 13 DISPLAY MESSAGES Mess Cause Outputs A02 ...

Page 4: ...in 5 Pr1 2oF Delay between DG compressor switch off and start up 0 to 999 sec 120 Pr1 odo Power on regulation delay 0 to 999 sec 5 Pr1 dSL Lower limit for control signal in percentage 0 function disabled 0 to 100 0 Pr2 Si0 Minimum input value in percentage 0 to 100 0 Pr2 Si1 Maximum input value in percentage 0 to 100 100 Pr2 PMi Minimum load in percentage 0 to 100 0 Pr2 PMA Maximum load in percent...

Reviews: