ZX Platform Condensing Unit
28
ZXD Family: Digital Medium Temperature
Capacity and Power (kW) at
50 Hz
- TFD
R22 - 50 Hz
Model
Ambient
Temperature
(
o
C)
Capacity
Evaporating Temperature (
o
C)
Power
Evaporating Temperature (
o
C)
-10
-5
0
5
10
12
-10
-5
0
5
10
12
ZXD0400
27
7.73
9.28
10.88
12.42
14.67
15.18
2.66
2.77
2.92
3.02
3.30
3.38
32
7.29
8.91
10.61
12.33
14.29
14.98
2.84
3.00
3.12
3.26
3.60
3.70
38
6.39
7.95
9.68
11.44
13.22
14.14
3.20
3.32
3.42
3.57
4.01
4.10
43
5.71
7.27
8.97
10.70
12.69
13.29
3.44
3.60
3.72
3.86
4.29
4.40
48
6.55
8.06
9.76
11.56
12.17
4.40
4.62
4.70
4.96
5.07
ZXD0500
27
8.76
10.44
12.22
14.12
17.28
18.22
3.03
3.18
3.29
3.47
3.95
4.10
32
8.31
9.96
11.72
13.68
16.62
17.47
3.35
3.57
3.67
3.97
4.50
4.58
38
7.69
9.28
11.06
13.06
15.31
16.34
3.87
4.07
4.27
4.47
4.98
5.10
43
6.80
8.36
10.15
12.21
14.60
15.47
4.27
4.47
4.66
4.96
5.46
5.56
48
7.62
9.49
11.47
13.49
14.40
5.44
5.61
5.80
6.01
6.04
ZXD0600
27
10.41
12.49
14.72
17.66
19.64
20.60
3.70
3.88
4.16
4.50
4.70
4.81
32
9.93
11.71
13.94
16.30
18.87
20.10
4.07
4.25
4.43
4.75
5.29
5.47
38
8.90
10.57
12.85
15.26
17.77
18.92
4.53
4.71
4.90
5.23
5.86
5.98
43
7.60
9.40
11.78
14.26
16.33
17.86
5.17
5.45
5.64
6.10
6.57
6.66
48
9.25
11.15
13.08
15.09
16.06
6.46
6.69
6.96
7.22
7.30
ZXD0750
27
12.37
14.91
17.73
20.87
4.54
4.76
4.98
5.22
32
11.24
13.90
16.96
20.21
4.95
5.19
5.51
5.91
38
10.85
13.25
16.08
19.42
5.53
5.83
6.25
6.80
43
12.29
15.09
18.49
6.43
6.93
7.62
ZXD0760
27
12.62
15.21
18.08
21.29
24.47
25.93
4.45
4.66
4.88
5.12
5.47
5.64
32
11.46
14.18
16.96
20.61
23.07
24.56
4.85
5.09
5.40
5.79
5.86
5.97
38
11.07
13.52
15.80
19.81
21.94
23.66
5.42
5.72
6.12
6.67
6.64
6.81
43
10.20
12.54
14.60
18.86
21.45
22.63
5.98
6.30
6.79
7.47
7.34
7.48
48
11.46
14.09
17.47
19.73
20.75
7.40
7.89
8.43
8.74
8.78
Notes:
Based on suction superheat of 10K.
Power include condenser fan.
Ambient 38