EM12-Z series user manual
26
P8-31
Any arrival frequency
detection amplitude 1
0.0%
~
100.0%
(
Maximum frequency
)
0.0%
√
P8-32
Any arrival frequency
detection value 2
0.00Hz
~
Maximum frequency
50.00Hz
√
P8-33
Any arrival frequency
detection amplitude 2
0.0%
~
100.0%
(
Maximum frequency
)
0.0%
√
P8-34
Zero current detection
level
0.0%
~
300.0%
100.0% corresponds to the motor rated current
5.0%
√
P8-35
Zero current detection
delay time
0.01s
~
600.00s
0.10s
√
P8-36 Output current over limit
0.0%
(
No detect
)
0.1%
~
300.0%
(
Rated current
)
200.0%
√
P8-37
Output current over limit
detect relay time
0.00s
~
600.00s
0.00s
√
P8-38 Any arrival current 1
0.0%
~
300.0%( Motor rated current)
100.0%
√
P8-39
Any arrival current 1
detect amplitude
0.0%
~
300.0%( Motor rated current)
0.0%
√
P8-40 Any arrival current 2
0.0%
~
300.0%( Motor rated current)
100.0%
√
P8-41
Any arrival current 2
detect amplitude
0.0%
~
300.0%( Motor rated current)
0.0%
√
P8-42
Timing function
selection
0: Invalid 1: Valid
0
√
P8-43
Timing of run time
selection
0: Set by P8-44
1: AI1
2: AI2
3: Potentiometer of operation panel
The range of analog input corresponds to P8-44
0
√
P8-44
Timing value setting of
running time
0.0Min
~
6500.0Min
0.0Min
√
P8-45
Lower limit of AI1 input
voltage protection
0.00V
~
P8-46
3.10V
√
P8-46
Upper limit of AI1 input
voltage protection
P8-45
~
10.00V
6.80V
√
P8-47
IGBT Module
temperature arrives
0
℃
~
100
℃
75
℃
√
P8-48 Cooling fan control
0: Working in running
1: Working after power up
0
√
P8-49 Wake up frequency
Sleep frequency (P8-51)
~
Maximum
(
P0-10)
0.00Hz
√
P8-50 Wake up delay time
0.0s
~
6500.0s
0.0s
√
P8-51 Sleep frequency
0.00Hz
~
Wake up frequency
(
P8-49)
0.00Hz
√
P8-52 Sleep relay time
0.0s
~
6500.0s
0.0s
√
P8-53
Current running arrival
time setting
0.0
~
6500.0 mins
0.0Min
√
P9 groupFault and protection
P9-00
Motor overload
protection selection
0: Prohibited1: Allow
1
√
P9-01
Motor overload
protection gain
0.20
~
10.00
1.00
√