MODBUS ADDRESS:30001 Temperature Value
MODBUS ADDRESS:30002 Led Status : 0.bit C Led,
6.bit Compressor Led,
13.bit Program Led, 14.bit Set Led
MODBUS ADDRESS:30003 Device Status :
1.bit Buzzer Status
2.bit Sensor Lost Status
MODBUS ADDRESS:30004 Output Status
MODBUS ADDRESS:30005 Device Type and Device Version
o
A
A
A
A
A
6.2 Modbus Adresses of Device Status Parameters (Read Input Register)
10
Buzzer is active during this time
When this parameter is 1, if decrement button is pressed, is observed. In this
condition buzzer is active till buzzer silence button is pressed.
( Default = ) MODBUS ADDRESS:40016
If buzzer function selection parameter value =0, this parameter can not be
observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
Programming Section Accessing Password
.
( Default = 0 ) MODBUS ADDRESS:40019
It is used for accessing to the programming section. It can be adjusted from 0 to 9999. If it is
selected 0, password will not be asked
PROKEY communication selected.
Communication Mode Selection Parameter
( Default = 0 ) MODBUS ADDRESS:40017
Rs485 communication selected.
Slave ID Parameter
( Default = 1 ) MODBUS ADDRESS=40018
Device communication address parameter (1 to 247).
,
,
,
,
and
Parameters are observed if Operation type
is selected “Cooling”. If operation type is selected “Heating ” ,skip to the
parameter
i
ENGLISH