2. Installation Instruction
What follows determines the validity of the warranty.
1. The installation must:
- Be performed by a qualified installer.
- Include, where necessary, a pressure reducer for the inlet water.
- Include a relief valve calibrated as shown on the technical data label
affixed to the boiler.
- Include an expansion tank (see expansion tank sizing table ) commen-
surate with the sizes of the boiler (it is recommended to arrange for the
calculations to be performed by a heating engineer).
2. Before start-up check tightening of the flange screws.
3. The temperature of the contents of the boiler must always be below
95°C.
4. Internal cleaning must be performed every 12 months.
5. To prevent corrosion the electronic anode supplied with the boiler
must be installed.
6. As is known, contact between different metals can cause corrosion.
In this sense, it is advisable to insert an appropriate dielectric cou-
pling between the attachments located inside the boiler and the
corresponding pipes.
7. The electrical conductivity of the water must not be less than 150 μS/
cm or greater than 1000 μS/cm.
Electronic anode
The boilers EURO V are delivered with nr. 1 electronic anode.
The connection for the electronic anode is located on the top of the boiler
(Attachment T).
The anode has an 1/2"M attachment: a reduction from 1”1/4M .
to 1/2"F is required (not supplied).
For the initial operation of the anode electronic see the manual supplied.
Expansion tank dimensioning
Values in litres relating to:
- pre-load pressure of 2.5 bar
- relief valve calibration pressure of 6.0 bar
- expansion from 10 to 90°C.
In systems with domestic water recirculation rings, the volume of the water in the pipes should also be considered.
Bracket Support
Led
Equipment
Electrode
Expansion tank
volume (I)
Boiler/Storage Model
150
200
300
500
40 °C
2,4
2,9
4,1
7,1
50 °C
3,8
4,6
6,4
11,2
60 °C
5,4
6,6
9,2
16,0
70 °C
7,2
8,8
12,3
21,4
80 °C
9,2
11,3
15,8
27,4
90 °C
11,4
14,0
19,5
34,0
Storage temperature