FG10071-1-0214
Page 6
Introduction
Always consult your local Building Department regarding regula-
tions, codes or ordinances which apply to the installation of a
vented decorative gas log set in a solid-fuel burning fireplace.
This appliance is only for use with the type of gas indicated on
the rating plate.
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installer must have owner fill out and mail warranty card
supplied with the fireplace.
3. Installer should show owner how to start and operate the
fireplace.
WARNING:
ANY CHANGE TO THIS APPLIANCE OR ITS CONTROLS
CAN BE DANGEROUS.
Improper installation or use of the appliance can cause se
-
rious injury or death from fire, burns, explosion or carbon
monoxide poisoning.
INTRODUCTION
General Information
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not
shown on the rating plate is the responsibility of the person
and company making the change.
Important
All correspondence should refer to complete Model No., Serial
No. and type of gas.
Notice:
During initial use of the ceramic logs and branches you
will detect an odor as the ceramic logs and branches are cured.
SPECIFICATIONS
MINIMUM FIREPLACE DIMENSIONS
MASONRY BUILT FIREPLACES
Chimney Height Minimum of 6 Feet
LOG SET
SIZE
FRONT
WIDTH IN
INCHES*
DEPTH IN
INCHES
HEIGHT IN
INCHES
MINIMUM
VENT
IN SQ.
INCHES
18”
24
18
18
49
24”
30
18
18
71
30”
36
18
18
71
MINIMUM FIREPLACE DIMENSIONS
FACTORY BUILT FIREPLACES
Chimney Height Minimum of 10 Feet
LOG SET
SIZE
FRONT
WIDTH IN
INCHES*
DEPTH IN
INCHES
HEIGHT IN
INCHES
MINIMUM
VENT
IN SQ.
INCHES
18”
24
18
18
49
24”
30
18
18
71
30”
36
18
18
71
*
Important:
When adding a valve kit to the burner, 8” needs to
be added to the front width dimension.
Note: Natural gas match throw sets may be used in some areas.
Check your local codes for this configuration.
WARNING
DO NOT use sand in Liquid Propane Hearth Kits. Use the Ver-
miculite, provided with the Liquid Propane Change Kit.
HEARTH
KIT SIZE
RATED
PRESSURE
(W.C.)
MAX GAS
PRESSURE
(W.C.)
ORIFICE
SIZE
BTU/HR
INLET
18”
7.0
10.5
27
60,000
24”
7.0
10.5
20
90,000
30”
7.0
10.5
16
90,000
HIGH ALTITUDE DERATE
In the U.S.A., input BTU shall be derated at 4% (1 orifice size)
per 1000 feet for altitudes above 2000 feet. In Canada, input BTU
shall be derated 10% (2 orifice sizes) at altitudes from 2000 feet
to 4500 feet.
ACCESSORIES
FGAFLMF
Valve Kit
FGRCAFLMFV
Motorized Hi/Lo Remote
FGRCAFLMF
ON/OFF Remote
FGLMFWWS
Wireless Wall Switch
FGAFVKSPMH/L
IP Pilot HI/LO Remote
FGAFVKSP
IP Pilot ON/OFF Remote