background image

35657-4-1015

Page 33

With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free 

service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified 

service person in the diagnosis of problems and the corrective action to be taken.

1.  Spark ignitor will not light pilot after repeated triggering 

of piezo ignitor button.

a.  Defective ignitor (no spark electrode) 

 

—Check for spark at electrode and pilot; if no spark and 

electrode wire is properly connected, replace ignitor.

b.  No gas or low gas pressure.

 

—Check  remote  shut  off  valves  from  fireplace.  Usually 

there is a valve near the main. There can be more than 

one (1) valve between the fireplace and main.

 

—Low pressure can be caused by a variety of situations 

such as a bent line, too narrow diameter of pipe, or low 

line pressure. Consult with plumber or gas supplier.

c.  No LP in tank. 

  —Check LP (propane) tank. Refill tank.

2.  Pilot will not stay lit after carefully following lighting 

instructions.

a.  Defective thermocouple.

 

—Check that pilot flame impinges on thermocouple. Clean 

and/or adjust pilot for maximum flame impingement.

 

—Ensure the thermocouple connection at the gas valve 

is fully inserted and tight (hand tight plus 1/4 turn). Faulty 

thermocouple if reading is below specified minimum of 15 

millivolts.

 

—Disconnect the thermocouple from the valve, place one 

millivolt meter lead wire on the end of the thermocouple 

and the other millivolt meter lead wire on the thermocouple 

copper wire. Start the pilot and hold the valve knob in. If 

the millivolt reading is less than 15 millivolt, replace the 

thermocouple.

b.  Defective valve.

 

—If thermocouple  is  producing  more  than  15  millivolts, 

replace faulty valve.

3.  Pilot burning, no gas to burner, valve knob “ON”, REMOTE/

OFF/ON switch “ON.”

a.  REMOTE/OFF/ON switch, wall switch, remote control or 

wires defective.

 

—Check REMOTE/OFF/ON switch and wires for proper 

connections. Place jumper wires across terminal at switch. 

If burner comes on, replace defective switch. If OK, place 

jumper wires across switch wires at gas valve-if burner 

comes on, wires are faulty or connections are bad.

b.  Thermopile may not be generating sufficient millivolts.

 

—If the pilot flame is not close enough physically to the 

thermopile, adjust the pilot flame.

 

—Be sure the wire connections from the thermopile at the 

gas valve terminals are tight and the thermopile is fully 

inserted into the pilot bracket.

 

—Check the thermopile with a millivolt meter. Take the 

reading at TH-TP & TP terminals of the gas valve. The 

meter should read 350 millivolts minimum, while holding the 

valve knob depressed in the PILOT position, with the pilot 

lit, and the REMOTE/OFF/ON switch in the OFF position. 

Replace the faulty thermopile if the reading is below the 

specified minimum. 

 

—With the pilot in the ON position, disconnect the thermopile 

leads from the valve. Take a reading at the thermopile leads. 

The reading should be 350 millivolts minimum. Replace 

the thermopile if the reading is below the minimum.

c.  Defective valve.

 

—Turn valve knob to ON. Place REMOTE/OFF/ON switch 

to ON. Check with millivolt meter at thermopile terminals. 

Millivolt meter should read greater than 200 millivolts. If 

the reading is okay and the main burner does not ignite, 

replace the gas valve.

d.  Plugged main burner orifice.

 

—Check main burner orifice for blockage and remove.

4.  Frequent pilot outage problem.

a.  Pilot flame may be too high or too low, or blowing (high), 

causing pilot safety to drop out.

 

—Clean and adjust flame for maximum flame impingement 

on  the  thermocouple.  Follow  lighting  instructions 

carefully.

5.  The pilot and main burner extinguish while in operation.

a.  No LP (Propane) in tank. 

 

Check LP (Propane) tank. Refill fuel tank.

b.  Inner vent pipe leaking exhaust gases back into system.

 

—Check for leaks.

c.  Glass too loose, gasket leaks in corners after usage.

 

—Be certain glass assembly is installed correctly.

d.  Horizontal vent improperly pitched.

 

—The horizontal vent cap should slope down only enough 

to prevent any water from entering the unit. The maximum 

downwards slope is 1/4 inch.

e.  Bad thermopile or thermocouple.

 

—Replace if necessary.

f.  Improper vent cap installation.

 

—Check for proper installation and freedom from debris 

or blockage.

6.  Glass soots, and/or soot deposits collected on logs.

a.  Flame impingement on logs incorrect.

 

—Check and adjust log position. See Page 17. Contact 

Empire Comfort Systems, Inc.

b.  Debris around throat of main burner.

 

—Inspect the opening at the base of the main burner. It is 

imperative that NO material be placed in this opening.

7.  Flame burns blue and lifts off main burner.

a.  Insufficient oxygen being supplied.

 

—Check to make sure vent cap is installed properly and 

free of debris. Make sure that vent system joints are tight 

and have no leaks.

 

—Check to make sure that no material has been placed 

at the main burner base.

STANDING PILOT TROUBLESHOOTING

Summary of Contents for DV25IN33LN-3

Page 1: ...n serious injury death or property damage Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas supplier from a neighbor s phone Follow the gas sup...

Page 2: ...mation 19 Log Identification 20 Log Placement 21 29 Operating Instructions 30 Standing Pilot Lighting Instructions 31 Standing Pilot Wiring 32 Standing Pilot Troubleshooting 33 IPI Electronic System Operating Instructions 34 IPI Electronic System Wiring Diagram 35 Intermittent Pilot Lighting Instructions 36 Intermittent Control System Troubleshooting 37 39 Insert Maintenance and Service 40 Insert ...

Page 3: ...WH Minimum 5 5 7 30 6 67 7 83 7 30 Orifice 53 0 0596 42 0 0935 1 55mm 36 0 1065 1 65mm 0 65 35 110 Air Shutter Opening Full Open 1 8 Full Open 1 4 Full Open 1 4 Gas Inlet Shutoff Valve pipe 1 2 NPT 1 2 NPT 1 2 NPT 1 2 NPT 1 2 NPT 1 2 NPT NOTE Air shutter settings are factory minimum settings Some venting configurations may require minor air shutter adjustments for optimum performance GAS SUPPLY PR...

Page 4: ...g to an existing round fireplace chimney pipe DVVK3FV Vertical Vent Kit 25 Two pieces of 25 FlexVent Rectangle Cap Flashing connectors and clamps Recom mended when installing to a square or rectangular clay flue DVK35 Vent Extension Kit 35 flex vent extension section with 2 connectors and 4 clamps NOTICE When installing vent caps special locally made flashings may be required to properly seal the ...

Page 5: ...an adjustable safety gate to keeptoddlers youngchildren andotherat riskindividuals out of the room and away from hot surfaces Definitions DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided c...

Page 6: ... manufacturing fabricating and shipping various components of this appliance are treated with certain oils films or bonding agents These bonding agents are not harmful but may produce annoying smoke and smells as they are burned off during initial operation of the appliance This is a normal temporary occurrence A window should be opened during the initial bake out period Keep burner and control co...

Page 7: ...gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a closed area and the odor intensity could vary at different levels Since it is heavier than air there may be more odor at lower levels Always be sensitive to the slightest gas odor If you detect any odor ...

Page 8: ...ause serious injury or death from fire burns explosions or carbon monoxide poisoning Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change Important All correspondence should refer to complete Model Number Serial Number and type of gas High A...

Page 9: ...e Opening Dimensional Information Sizing MINIMUM FIREPLACE OPENING DIMENSIONS MODEL NO HEIGHT A FRONT WIDTH B DEPTH C REAR WIDTH D DV25IN 18 3 8 27 1 2 12 3 4 17 1 4 DV33IN 21 3 8 30 1 2 14 1 4 19 DV35IN 23 3 8 33 1 2 14 1 4 22 NOTICE If the fireplace lintel is wider than 8 203mm the height of the fireplace opening must be increased a few inches to allow for a gradual offset in the exhaust and or ...

Page 10: ...istance from Face of Fireplace Height Above Top of Insert A 10 N 23 B 9 1 4 O 22 C 8 3 4 P 21 D 8 Q 20 E 7 1 4 R 19 F 6 1 2 S 18 G 6 T 17 H 5 1 4 U 16 I 4 1 2 V 15 J 3 3 4 W 14 K 3 X 13 L 2 1 2 Y 12 M 1 3 4 Z 11 Figure 3 Combustible Material No greeting cards stockings or ornamentation of any type should be placed on or attached to the fireplace The flow of heat can ignite combustibles ...

Page 11: ...ble by the authority having jurisdiction The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length Figure 4 Gas Supply Pressure inches w c Minimum Normal Maximum Natural Gas 4 5 7 0 14 0 LP Propane 10 8 11 0 14 0 Manifold Pressure inches w c Normal HI Natural Gas 3 5 LP Propane 10 0 Installing a New Main Gas Cock Each appliance should have its own m...

Page 12: ... equal to or less than 1 2 psig 3 5kPa Attention If one of the procedures results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the fireplace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural gas valves have a built in pressure regulator in the gas valve Natural gas models will have a manifold pressure of approximately 3 5 w c 871kPa at t...

Page 13: ...the solid fuel fireplace it is installed into NOTICE Cutting of sheet metal parts of a fireplace in order to install the fireplace insert is prohibited WARNING Only surrounds shrouds and decorative front components supplied by the manufacturer may be used to cover integral grills on the solid fuel burning fireplace No other compo nents such as sheet metal plates may be used to seal off vents 7 To ...

Page 14: ...tory built wood burning fireplace the use of the DVKI Round Vertical Termination Kit should allow you to mount the vent adaptor and cap to the exposed round chimney pipe easily Connecting the Vent Pipe CAUTION Sharp edges Always use gloves when installing Install the 3 inch flexible vent pipes down through the chimney Attach the pipe to cap adaptor to the termination cap and the top of the flexibl...

Page 15: ...LUE EXHAUST VENT ROUND TERMINATION CAP DVKI KIT ROUND CO LINEAR TO CO AXIAL ADAPTOR 10 MINIMUM 35 MAXIMUM USE HIGH TEMP SEALANT ON VENT CONNECTIONS SCREWS ADDED THROUGH VENT CLAMPS TO RETAIN VENTING TO COLLARS RECOMMENDED USE HIGH TEMP SEALANT ON VENT CONNECTIONS RETAINER SCREWS MAY BE INSTALLED THROUGH THE VENT CLAMPS TO ENSURE POSITIVE SECUREMENT OF VENTING VENT CLAMPS NOTE LONG EXTENSION TUBE F...

Page 16: ...offset pipe every 4 This application will require that you first determine the roof pitch and use the appropriate venting components General Maintenance Conduct an inspection of the venting system semi annually Recommended areas to inspect are as follows 1 Check areas of the venting system which are exposed to the elements for corrosion These will appear as rust spots or streaks and in extreme cas...

Page 17: ...to the log support and set aside 3 Remove the rear log support by removing the three screws securing it to the firebox and set aside 4 Loosen the two bottom screws that secure the inlet air duct collar at the rear of the firebox See Figure 12 5 Place the inlet air restrictor plate over the air intake opening Align the plate with the loosened screws shift the plate on the keyhole slots then retight...

Page 18: ...ove the switch knockout on the side surround panel then install the ON OFF switch 5 Connect the low voltage wires from the gas valve to the ON OFF switch 6 Attach the surround panel assembly to the insert Place the surround panel assembly against the face of the insert and align the lower retaining tabs with the notches on the insert sides Lift the surround panel assembly slightly until the bot to...

Page 19: ...er speed and BTU input level setting control by adjustment of the HI LO knob located on the gas valve Blower removal instructions Servicing or removal of the blower system must be performed by a qualified service person If the blower assembly must be replaced the following steps are recommended for removal 1 Turn off gas and disconnect the electrical supply 2 Remove the glass door assembly 3 Remov...

Page 20: ...ge 20 LOG IDENTIFICATION Log Description Part Number Front View Top View DV25IN DV 33 35 IN Log A R9256 R9218 Log B R9257 R9219 Log C R9255 R9217 Log D R9259 R9251 Log E R9258 R9220 Log F R9260 R9252 Log G R9261 R9253 ...

Page 21: ...rd approximately 10 15 degrees then grasping the edges gently lift upward to remove the door assembly and set aside 5 Remove the foam packaging that contains the log set from inside the firebox 6 Carefully unpack the logs and twigs Spread them out for easy identification Note Continue to pages 21 29 for step by step instructions with images Figure 18 WARNING Failure to position the parts in accord...

Page 22: ...35657 4 1015 Page 22 1 Place Log A on the front log support ledge between the left tab and the grate tangs Log A will touch the back of the grate tangs See image below LOG PLACEMENT ...

Page 23: ...35657 4 1015 Page 23 2 Place Log B on the front log support ledge between the left tab and the grate tangs Log B will touch the back of the grate tangs See image below LOG PLACEMENT ...

Page 24: ...the rear log support that keep the back log positioned correctly DV33IN models have one small tab in the rear log support to ensure the back log is in the correct position The DV35IN models will have two tabs bent forward in the rear log support to ensure proper left to right positioning of the log plus one small tab near the center that keeps the back log from shifting forward See image below LOG...

Page 25: ...les on the bottom flat surface Align the two holes with the two left pins on the burner assembly Make sure this log is not raised up off of the burner The flat bottom surface must be completely resting flat on the top of the burner surface See image below LOG PLACEMENT ...

Page 26: ...oles on the bottom flat surface Align these two holes with the two right pins on the burner assembly Make sure this log is not raised up off of the burner The flat bottom surface must be completely resting flat on the top of the burner surface See image below LOG PLACEMENT ...

Page 27: ... Page 27 6 Add Log F by placing the locator pin hole on the bottom of the twig with the pin on top of the center right log The tip of Log F will rest on top of Log C near the right end See image below LOG PLACEMENT ...

Page 28: ... hole on the bottom of the log with the pin on top of Log D The long branch of Log G will rest in a small groove on top of Log C Note The flat side of the log will face the left side liner This groove is near the left end of Log C See image below LOG PLACEMENT ...

Page 29: ... door assembly onto the fireplace insert 10 Secure the glass door with the two spring clamps located under the firebox 11 Re install the upper and lower louver assemblies by aligning the end tabs with the slots provided in the outer face flanges of the insert LOG PLACEMENT ...

Page 30: ...ot flame to operate an additional one 1 to two 2 minutes before you turn the gas control knob from the PILOT position to the ON position This time period allows the millivolts electrical current to build up to a sufficient level allowing the gas control to operate properly 1 Follow the SAFETY and LIGHTING INSTRUCTIONS for standing pilot controls found in this manual and on labels found in control ...

Page 31: ...F ON switch to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B Before lighting smell all around the appliance area for gas Be sure to...

Page 32: ...G minimum wire and connect it to the fireplace valve pigtails WARNING DO NOT CONNECT THE 110 120 VAC TO THE WALL SWITCH OR THE CONTROL VALVE WILL BE DESTROYED WARNING LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROL WIRING ERRORS CAN CAUSE IM PROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING WARNING Electrical Grounding Instructions This appliance is equipped with...

Page 33: ...tions from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading at TH TP TP terminals of the gas valve The metershouldread350millivoltsminimum whileholdingthe valve knob depressed in the PILOT position with the pilot lit and the REMOTE OFF ON switch in the OFF position Replace th...

Page 34: ...ual and on labels found in the control compartment located in the lower cavity of the appliance 2 During the operating season or in power outage periods it is recommended that the pilot remain in the CPI standing pilot mode to reduce cold start issues and or conserve battery backup power during a power outage 3 The gas valve has inlet and outlet pressure taps as shown in Figure 23 Refer to pages 8...

Page 35: ... is used CAUTION Do not operate the appliance with panel s removed cracked or broken Replacement of the panel s should be done by a licensed or qualified service person WARNING Improper installation adjustment alteration service or mainte nance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer service agency or the gas sup...

Page 36: ...er several tries turn the gas cock clockwise to OFF and call your service technician or gas supplier 11 Replace the front surround assembly or close bottom louver assembly 12 Operation of the gas valve is controlled by a manual on off switch or a hand held remote control Refer to remote instructions for detailed operation information LIGHTING INSTRUCTIONS A This appliance has a pilot which must be...

Page 37: ...23 Troubleshooting Before proceeding with the procedures in the following trouble shooting table verify that the power supply AC DC adapter is present and that the batteries inside the receiver and or optional battery pack are fresh and installed with correct polarity Make sure all the connections between the wire harnesses and system components are proper and positive Verify that the static inlet...

Page 38: ...35657 4 1015 Page 38 INTERMITTENT CONTROL SYSTEM TROUBLESHOOTING ...

Page 39: ...35657 4 1015 Page 39 INTERMITTENT CONTROL SYSTEM TROUBLESHOOTING ...

Page 40: ...t abuse the glass by striking or hitting the glass Although the frequency of servicing and maintenance will depend on use and the type of installation you should have a qualified service technician perform an appliance checkup at the beginning of each heating season Specific guidelines regarding each appliance maintenance task are listed below Glass Door Installation 1 When installing the Glass Do...

Page 41: ... 4 6 7 45 43 1 2 3 1 9 17 19 18 22 23 31 21 24 20 13 26 27 30 29 28 15 30 16 25 12 48 49 51 50 53 54 55 52 56 57 WARNING Failure to position parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury ...

Page 42: ...436 R3436 R3436 SWITCH REMOTE OFF ON 16 R2708 R2708 R2708 R2708 R2708 R2708 IGNITER PIEZO 17 26141 26141 25550 25550 25551 25551 LOG SUPPORT REAR 18 25547 25547 25547 25547 FLAME SHIELD RIGHT 19a R7612 R10423 R7612 R10423 R7612 R10423 PILOT ASSEMBLY NAT 19b R7611 R10424 R7611 R10424 R7611 R10424 PILOT ASSEMBLY LP 20 R9189 R9189 R9189 R9189 R9189 R9189 GASKET PILOT 21 R5676 R5676 R5676 R5676 R5676 ...

Page 43: ...MBLY W MOUNTING PLATE PAD 46 R2204 R2204 R2204 R2204 R2204 R2204 CORD SET 47 R10961 R10961 R10961 R10961 R10961 R10961 FLEXLINE W SHUTOFF VALVE 48 R2423 R2423 R2423 R2423 R2423 R2423 CONNECTOR MALE 49 29382 29382 29382 TRAY MODULE 50 R2667 R2667 R2667 WIRE 5 1 2 BLACK QTY 2 51 R2522 R2522 R2522 ON OFF SWITCH 52 R11122 R11122 R11122 BATTERY HOLDER 53 R11127 R11127 R11127 DFC CONTROL BOARD 54 R11123...

Page 44: ...n be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Number not the Index Number and the Description of each part from the fol lowing illustration and part list Be sure to gi...

Page 45: ...ust be installed by a qualified installer and operated in accordance with the instructions furnished with the ap pliance A bill of sale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might result from the use misuse or improper installation of this appliance Travel dia...

Page 46: ...35657 4 1015 Page 46 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes ...

Page 47: ...35657 4 1015 Page 47 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes ...

Page 48: ...mpire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact your dealer ...

Reviews: