28365-2-0811
Page 20
MAXIMUM HORIZONTAL
RUN WITH NO VERTICAL
RISE AND 90° ELBOW
MAXIMUM HORIZONTAL
RUN WITH MINIMUM
VERTICAL RISE AND
90° ELBOW
minimum
Figure 26
Figure 27
FIREpLACE
SERIES
HARD ELBOW DIMENSIONS
"A"
"B"
"C"
"D"
DVCD32FP
41-1/2"
(1054 mm)
4"
(102 mm)
6"
(152 mm)
9 1/8"
(232 mm)
DVCD36FP
41-1/2"
(1054 mm)
4"
(102 mm)
6"
(152 mm)
9 1/8"
(232 mm)
DVCD42FP
43-1/2"
(1105 mm)
4"
(102 mm)
6"
(152 mm)
9 1/8"
(232 mm)
FIREpLACE
SERIES
FLEX pIpE 90 DEGREE BEND
"A"
"B"
"C"
"D"
DVCD32FP
43"
(1092 mm)
4-1/2"
(114 mm)
6-1/2"
(165 mm)
9 1/8"
(232 mm)
DVCD36FP
43"
(1092 mm)
4-1/2"
(114 mm)
6-1/2"
(165 mm)
9 1/8"
(232 mm)
DVCD42FP
45"
(1143 mm)
4-1/2"
(114 mm)
6-1/2"
(165 mm)
9 1/8"
(232 mm)
Figure 25
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH
THE WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE
ELBOW OFF TOp OF FIREpLACE
SEE FIGURE 21 ON pAGE 18 FOR pERMISSIBLE "H" AND "V"
DIMENSIONS.
VENTING FIREpLACE - TOp (continued)
positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two (2) studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole (Figures 25)
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 10" (254mm) high x 10" (254mm) wide with its center line
determined by the amount of vertical rise and horizontal run of the
termination. (See Figure 25) When locating the hole it must be noted
that the bottom of the cap must be 12" (305mm) above the ground
level, and top of the cap must be no less than 18" (457mm) below a
combustible projection, and no closer than 9" (229mm) to any wall
running parallel to vent termination. (See Figure 26)
B
C
A
CENTER OF ELBOW
STRAIGHT OUT
(MINIMUM)
D
C
B
V