background image

38746-0-0118

Page 15

For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in 

whole or in part for residential purposes, including those 

owned or operated by the Commonwealth and where the 

side wall exhaust vent termination is less than seven feet 

above finished grade in the area of the venting, including 

but not limited to decks and porches, the following 

requirements shall be satisfied:

1.  INSTALLATION OF CARBON MONOXIDE 

DETECTORS. At the time of installation of the side 

wall horizontal vented gas fueled equipment, the 

installing plumber or gasfitter shall observe that a hard 

wired carbon monoxide detector with an alarm and 

battery back-up is installed on the floor level where 

the gas equipment is to be installed. In addition, 

the installing plumber or gasfitter shall observe that 

a battery operated or hard wired carbon monoxide 

detector with an alarm is installed on each additional 

level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. 

It shall be the responsibility of the property owner to 

secure the services of qualified licensed professionals 

for the installation of hard wired carbon monoxide 

detectors.

 

a.  In the event that the side wall horizontally vented 

gas fueled equipment is installed in a crawl space 

or an attic, the hard wired carbon monoxide 

detector with alarm and battery back-up may be 

installed on the next adjacent floor level.

 

b.  In the event that the requirements of this 

subdivision can not be met at the time of 

completion of installation, the owner shall have 

a period of thirty days to comply with the above 

requirements; provided, however, that during 

said thirty day period, a battery operated carbon 

monoxide detector with an alarm shall be installed.

2.  APPROVED CARBON MONOXIDE DETECTORS. 

Each carbon monoxide detector as required in 

accordance with the above provisions shall comply 

with NFPA 720 and be ANSI/UL 2034 listed and IAS 

certified. 

3.  SIGNAGE. A metal or plastic identification plate 

shall be permanently mounted to the exterior of the 

building at a minimum height of eight feet above grade 

directly in line with the exhaust vent terminal for the 

horizontally vented gas fueled heating fireplace or 

equipment. The sign shall read, in print size no less 

than 1/2 inch in size, 

GAS VENT DIRECTLY BELOW. 

KEEP CLEAR OF ALL OBSTRUCTIONS

.

4.  INSPECTION. The state or local gas inspector of the 

side wall horizontally vented gas fueled equipment 

shall not approve the installation unless, upon 

inspection, the inspector observes carbon monoxide 

detectors and signage installed in accordance with the 

provisions of 248 CMR 5.08(2)(a) 1 through 4.

 

(b)  EXEMPTIONS: The following equipment is exempt 

from 248 CMR 5.08(2)(a)1 through 4: 

 

 

1.  The equipment listed in Chapter 10 entitled 

Equipment Not Required To Be Vented

 in the 

most current edition of NFPA 54 as adopted by 

the Board; and 

 

 

2.  Product Approved side wall horizontally vented 

gas fueled equipment installed in a room or 

structure separate from the dwelling, building 

or structure used in whole or in part for 

residential purposes. 

 

(d)  MANUFACTURER REQUIREMENTS - GAS 

EQUIPMENT VENTING SYSTEM NOT 

PROVIDED. When the manufacturer of a Product 

Approved side wall horizontally vented gas fueled 

equipment does not provide the parts for venting 

the flue gases, but identifies 

special venting 

systems

, the following requirements shall be 

satisfied by the manufacturer:

 

 

1.  The referenced 

special venting system

 

instructions shall be included with the fireplace 

or equipment installation instructions; and

 

 

2.  The 

special venting systems

 shall be Product 

Approved by the Board, and the instructions 

for that system shall include a parts list and 

detailed installation instruction.

 

(e)  A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled 

equipment, all venting instructions, all parts lists 

for venting instructions, and/or all venting design 

instructions shall remain with the fireplace or 

equipment at the completion of the installation. 

REQUIREMENTS FOR MASSACHUSETTS

Summary of Contents for DVCT36CBP95N-1

Page 1: ...LOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediat...

Page 2: ...the fireplace This is a heating appliance The flow of heat can ignite combustibles Figure 1 GENERIC MODEL SHOWN COMBUSTIBLE MATERIAL TABLE OF CONTENTS SECTION PAGE Multifunction Remote Operating Instructions 3 9 Lighting Instructions 10 Maintenance And Service 11 12 Important Safety Information 13 Safety Information For Users Of Propane Gas 14 Requirements For Massachusetts 15 Warranty Back Cover ...

Page 3: ... operating the remote system or activating manual bypass of the remote system CAUTION PROPERTY DAMAGE HAZARD EXCESSIVE HEAT CAN CAUSE PROPERTY DAMAGE The appliance can stay lit for many hours Turn off the appliance if it is not going to be attended for any length of time Always place the Transmitter where children can not reach it Figure 2 Figure 3 NOTE This control system includes a Battery Back ...

Page 4: ...with a paper clip and the IFC module will beep three times to indicate the IFC module is ready to synchronize with the transmitter within ten seconds See Figure 5 Figure 4 SWI BUTTON Figure 5 5 With the batteries already installed in the Transmitter push the On button The Receiver will beep four times to indicate the Transmitter s command is accepted and sets to the par ticular code of that Transm...

Page 5: ...m the Receiver confirms reception of the command Remote Control Display Figure 9 Remote Flame Control The Proflame has six flame levels With the system on and the flame level at the maximum in the appliance pressing the Down Arrow Button once will reduce the flame height by one step until the flame is turned off The Up Arrow Button will increase the flame height each time it is pressed If the Up A...

Page 6: ... Transmitter Operation The Smart Thermostat function adjusts the flame height in accordance to the difference between the set point temperature and the actual room temperatures As the room temperature gets closer to the set point the Smart Function will modulate the flame down To activate this function press the Thermostat Button until the word SMART appears to the right of the temperature bulb gr...

Page 7: ...lit Flow To activate this function use the Mode Button Figure 3 to index to the SPLIT FLOW mode icon See Figures 22 and 23 Pressing the Up Arrow Button will activate the secondary burner Pressing the Down Arrow Button will turn the secondary burner off A single beep will confirm the reception of the command OFF Figure 22 MULTIFUNCTION REMOTE OPERATING INSTRUCTIONS OFF Figure 23 Remote Auxiliary Re...

Page 8: ... to avoid unsupervised operation To activate this function press the MODE and UP Buttons at the same time See Figure 28 To deactivate this function press the MODE and UP Buttons at the same time OFF Figure 28 Low Battery Power Detection Transmitter The life span of the remote control batteries depends on various factors quality of the batteries used the number of ignitions of the appliance the num...

Page 9: ... the wall control or remote control OFF for two or three seconds and then restoring a power supply back on The return of the system to normal operation must be checked under safe conditions by the user and or service personnel Using the Fireplace without a Remote Control The fireplace can be turned ON HI only and OFF with the wall switch The fireplace flame ON OFF is the only function that will op...

Page 10: ... force LIGHTING INSTRUCTIONS 1 STOP Read the safety information above 2 Turn OFF electric power to the appliance 3 Turn gas shutoff knob counterclockwise to ON position 4 Wait ten minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above on this label If you do not smell gas go to the next step 5 Turn ON electric power t...

Page 11: ...nd at least annually Inspect the external vent cap on a regular basis to make sure no debris is interferes with the air flow Cleaning the Glass Clean the glass periodically We recommend gas fireplace glass cleaner During start up condensation forms on the inside of the glass causing lint dust and other airborne particles to cling to the glass Also initial paint curing may deposit a film on the gla...

Page 12: ... GLASS LATCH 4 PLACES L A T C H LA T C H LA T C H Figure 31 Light Bulb s Replacement 1 Remove the following items barrier screen glass frame assembly This unit comes standard with two lights that are attached to the roof of the fireplace To access the light bulb you will remove the following items by removing four screws per light See Figure 32 metal bezel glass gasket NOTE Use gloves when handlin...

Page 13: ...l an adjustable safety gate to keep toddlers young children and other at risk individuals out of the room and away from hot surfaces The vent cap located on the outside of your home will also become very hot Alert everyone adults and children to stay clear and avoid touching the vent cap Keep the area around the vent cap clear of combustibles including shrubs and trees Do not use this fireplace if...

Page 14: ...d gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity Propane Gas may stratify in a closed area and the odor intensity could vary at different levels Since it is heavier than air theremaybemoreodoratlowerlevels Alwaysbesensitive to the slightest gas odor If you detect any odor tr...

Page 15: ...20 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating fireplace or equipment The sign shall read in print size no less than 1 2 inch in size GAS VENT DIRE...

Page 16: ...the instructions furnished with the appliance A bill of sale canceled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might result from the use misuse or improper installation of this appliance Travel diagnostic costs and freight charges on warranted parts to and from the factory...

Reviews: