26988-3-1012
Page 37
FOR FIREPLACE MODEL: ADVD32FP34N, USE CONVERSION KIT PART NUMbER 19553 (Included with Fireplace)
FOR FIREPLACE MODEL: ADVD36FP34N, USE CONVERSION KIT PART NUMbER 19554 (Included with Fireplace)
FOR CONVERSION TO
LIQUEFIED PETROLEUM (LP) GAS
WARNING:
This conversion kit is to be installed by an Empire Comfort Systems, Inc., distributor (or other qualified agency¹)*in
accordance with the manufacturer’s instructions and all codes and requirements of the authority having jurisdiction. Failure to follow
instructions could result in serious injury or property damage. The qualified agency performing this work assumes responsibility for this
conversion.
*The term “qualified individual, firm, corporation or company which either in person or through a representative is engaged in and is
responsible for (a) the installation of gas piping or (b) the connection, installation repair, or servicing of equipment, who is experienced
in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.
CHECK SAFETY SHUTDOWN PERFORMANCE
SAFETY SHUTDOWN SYSTEM
Continuous Ignition Systems (Standing Pilot)
1. Place gas control knob in PILOT position. Main burner should go off and pilot should remain lit.
2. Extinguish pilot flame. Pilot gas flow should stop within 30 seconds. Safety shutoff of pilot gas proves complete shutdown since
safety shutoff valve blocks flow of gas to main burner and pilot.
3. Relight pilot burner and operate system through one complete cycle to make sure all controls operate properly.
WARNING
Perform the safety shutdown test anytime work is done on a gas system to avoid the possibility of fire or explosion with
property damage, personal injury or loss of life.
Gas input for direct vent fireplace converted to Propane (LP) gas:
ADVD32 18,000 BTU per hour
ADVD36 20,000 BTU per hour
The direct vent gas fireplace when converted to Propane (LP) gas will have a manifold pressure approximately 10.0" w.c. (2.49 kPa) for
a maximum input or 4.5" w.c. (1.120 kPa) for a minimum input at the valve outlet with the inlet pressure to the valve from a minimum of
10.8" w.c. (2.68 kPa) for the purpose of input adjustment to a maximum of 14.0" w.c. (3.484 kPa).
PARTS LIST
PART
DESCRIPTION
KIT 19553
KIT 19954
qUANTITY
SUPPLIED
Pilot Orifice
R-7658
R-7658
1 EA.
Main Burner Orifice
P-287
P-182
1
Sit Gas Valve
Conversion Kit
R-7657
R-7657
1
Gas Conversion
Label
19553-2136
19954-2136
1
GAS CONvERSION INSTRUCTIONS