background image

32186-0-0513

Page 6

Here are some suggestions.

1.  If you have a choice, select a location close to the chimney.

2.  If there is no chimney, you will have to run a flue pipe from the 

furnace, up to and above the house roof. 

see Figure 1.

  Select 

a location permitting the most direct run.  Try going up to the 

roof through a closet.  Remember that the flue pipe must slope 

upwards at least 1/4 of an inch for each foot and you may find 

floor joints in our path, so it is important to plan the run carefully. 

see Figure 8.

Figure 8

3.  If you have decided to go up to the roof through a closet, re-

member that you MUST keep a minimum distance of 1 inch 

between Type B vent pipe and any combustible material. 

see 

Figure 9

. Run it through a single wall pipe that is 2 inches 

larger in diameter than the flue pipe.  Use thimbles when going 

through floor and ceiling and flashing when going through roof.

Figure 9

Figure 5

10.  When connecting the flue pipe to the chimney, the pipe MUST 

go fully in and be cemented. 

see Figure 7.  

The flue pipe MUST 

NOT go too far into the chimney.  It should be cut off as it will 

interfere with normal venting. 

see Figure 7.

11.  The flue pipe MUST be sealed.  No open "Tees." 

see Figure 

5.

Figure 6

12.  The flue pipe's vertical rise MUST always be at least twice the 

length of the horizontal run.

Figure 7

Summary of Contents for 3588-4

Page 1: ...tructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vici...

Page 2: ...This series is design certified in accordance withAmerican National Standard Z21 86b 2002 by the Canadian Standards Association as a gravity type Floor Furnace and must be installed according to these...

Page 3: ...be required due to excessive lint from carpeting bedding materials etc It is imperative thatcontrolcompartments burners andcirculating air passageways of the appliance be kept clean Do not use this h...

Page 4: ...as can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clos...

Page 5: ...sulated single wall metal pipe shall not be used outdoors in cold climates for venting gas utilization equipment 4 For flue pipe running through walls roof and within one 1 inch of combustible constru...

Page 6: ...the roof through a closet re member that you MUST keep a minimum distance of 1 inch between Type B vent pipe and any combustible material See Figure 9 Run it through a single wall pipe that is 2 inche...

Page 7: ...ion the additional furnace support and then nail the support in place by driving three nails into each end of it through the headers See Figure 10 12 Remove the jacks and supports 13 Make sure the fur...

Page 8: ...ce between two joists because location is critical See Figure 10 If the location is not critical it is easier for you to put the furnace against a joist and then fill in with one additional support Do...

Page 9: ...nominal pipe thread Use at least 1 2 inch pipe to avoid excessive pressure drop check lo cal codes Install the piping in accordance with the requirements described in Installation Planning Compounds...

Page 10: ...average with the thermostat ON 140 minimum for valve to open 65 minimum for pilot to stay on Caution Label all wires prior to disconnection when servic ing controls Wiring errors can cause improper an...

Page 11: ...TE The gas control rod is attached to the gas control knob 4 Push in gas control rod slightly and turn clockwise to OFF Note Rod cannot be turned from PILOT to OFF un less rod is pushed in slightly Do...

Page 12: ...ural gas models should have a manifold pressure of approximately 3 5 w c at the valve outlet with the inlet pressure to the valve from a minimum of 5 0 w c for the purpose of input of input adjustment...

Page 13: ...ust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS...

Page 14: ...32186 0 0513 Page 14 20 21 22A 22B 23 24 25 EXPLODED VIEW...

Page 15: ...15L PILOT BURNER WITH THERMOPILE LP GAS 12 602032 23218 23217 BURNER 13 732010 FF250 FF250 ELECTRODE AND WIRE 14 R2313 R2313 R2313 PIEZO IGNITOR 15 742169 P8631 P8625 BURNER ORIFICE NATURAL GAS 15 742...

Page 16: ...ppliance for service What Is Not Covered Damages that might result from the use misuse or improper installation of this appliance Travel diagnostic costs and freight charges on warranted parts to and...

Reviews: