Page 8

The vent terminal of a direct vent appliance, with an input of 10,000 

Btu per hour (3 kW) or less shall be located at least 6" (150mm) 

from any air opening into a building, and such an appliance with an 

input over 10,000 Btu per hour (3 kW) but not over 50,000 Btu per 

hour (14.7 kW) shall be installed with a 9" (229mm) vent terminal 

clearance and the bottom of the vent terminal and the air intake 

shall be located at least 12" (305mm) above grade.  

WarninG: 

 The nearest point of the vent cap should be a 

minimum horizontal distant of six (6) feet (1.8m) from any 

pressure regulator.  In case of regulator malfunction, the six 

(6) feet (1.8m) distance will reduce the chance of gas entering 

the vent cap.

1.  In selecting a location for installation, it is necessary to provide 

adequate  accessibility  clearances  for  servicing  and  proper 

installation.

2.  Although certified for 0 clearance to the floor , the  unit is held in 

place by a wall bracket.  Enough clearance [2" (51mm) suggested] 

to allow changing or adding floor covering is recommended.  

Other clearances to combustible construction:  

  Sides 1" (25mm) and 12" (305mm) from the top. 

3.  Note the position of the vent relative to the center of the unit. 

The DV-210 has the vent in the center.  The  DV-215 vent is 2" 

(51mm) off center to the right.

4.  The minimum distance from the center of the outside vent  to 

the nearest outside corner or obstruction is 16" (406mm).

5.  The DV-210/DV-215 minimum wall depth is 4 1/2" (114mm) 

and maximum wall depth is 13" (330mm).  The use of tubes 

not  supplied  by  the  manufacturer  result  in  unsatisfactory 

performance.

The furnace is to be located on an outside wall.  Locate wall studs 

so that wall opening will be located between wall studs.  One wall 

stud can be used for attachment of inside wall plate.  The wall 

opening required as shown in Figure 3 is a minimum diameter 

of 6 1/4 (159mm) inches.  The inside wall plate and the outside 

wall plate are large enough to permit a wall opening diameter of 

8 inches (203mm).

A template is provided in furnace carton for positioning furnace 

on the wall.  Also, refer to Figure 3 for positioning the furnace on 

wall and for locating gas line connection.

Figure 3

installing inside Wall Plate

After the wall opening has been located and cut, center and level 

inside wall plate in wall opening.  The collar on the inside wall 

plate is to be placed within the wall opening.  On solid wall or wall 

stud, attach inside wall plate with (6)  #10 x 1 1/2" (38mm) screws 

provided.  On sheet rock wall, by using wall opening for access, 

attach inside wall plate with (6) #10 x 1 1/2" (38mm) screws and 

(6) Tinnerman nuts provided.  

Attaching Furnace To Inside Wall Plate

Align and attach mounting clips on furnace back with mounting 

slots on inside wall plate.  The furnace support bracket located 

at furnace bottom is to be secured to wall.  On solid wall, secure 

furnace  support    bracket  with  (1)  #10  x  1  1/2"  (38mm)  screw 

provided.  On sheet rock wall, secure furnace support bracket with 

(1) toggle bolt provided.

Figure 4

(64mm)

(13mm)

clearances

installation instructions

Summary of Contents for DV-210-SG

Page 1: ...th or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vicin...

Page 2: ...ifications 6 Gas Supply 7 Clearances 8 Installation Instructions 8 9 Thermostat Location 10 Lighting Instructions 11 Pilot Flame Characteristics 12 Main Burner Flame Characteristics 12 Maintenance 12...

Page 3: ...ied service person More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is impera tive that control compartments burners and circulating air passageways...

Page 4: ...g vehicle trailer or area Finally let the service man and firefighters check for escaped gas Have them air out the area before you return Properly trained LP Gas service people should repair the leak...

Page 5: ...uiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to the exter...

Page 6: ...erformed only by a qualified agency The term qualified agency meansanyindividual firm corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible for a the in...

Page 7: ...that a drip line be installed near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign partic...

Page 8: ...nimum wall depth is 4 1 2 114mm and maximum wall depth is 13 330mm The use of tubes not supplied by the manufacturer result in unsatisfactory performance The furnace is to be located on an outside wal...

Page 9: ...l Remove 5 127mm diameter air inlet tube from collar of air drop assembly 2 Attach3 76mm diameterflueoutlettubeontoflueoutletcollar oncombustionchamber Besure3 76mm diameterflueoutlet tube is placed a...

Page 10: ...d be Across the thermopile terminals 400 450 millivolts with ther mostat off Across the thermopile terminals 150 250 millivolts with ther mostat on Across the thermostat wires at the valve less than 3...

Page 11: ...to desired setting 16 CAUTION Pilot access cover must be kept tightly closed during operation To Turn Off Gas To Appliance FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these inst...

Page 12: ...ted After this the valve and orifice elbow can be removed as a unit Cleaning The Pilot Burner Cleaning of the pilot may be an annual necessity due to spiders After removing the supply tubing and orifi...

Page 13: ...properly size orifice 4 Pilot and main burner go out during normal operation a Check millivolts b Check for proper size of pilot flame c Check for defective or weak thermopile d Check input reduce as...

Page 14: ...HOLE 11 852098 NUT FOR ORIFICE FITTING 12 742134 BURNER ORIFICE DV 210 NAT 12 742133 BURNER ORIFICE DV 215 NAT 12 742297 BURNER ORIFICE DV 210 LPG 12 742282 BURNER ORIFICE DV 215 LPG 13 742038 ORIFICE...

Page 15: ...12433 10 0109 Page 15 PARTS VIEW...

Page 16: ...appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong re ceptacle Do not cut or remove th...

Page 17: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: