background image

19563-3-0907

Page 7

Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/
CGA-B149 (.1 or .2) installation code.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Inside Diameter

Tubing, Type L 

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10 feet

0-3 meters

1/2”

12.7mm

3/8”

9.5mm

1/2”

12.7mm

3/8”

9.5mm

10-40 feet

4-12 meters

1/2”

12.7mm

1/2”

12.7mm

5/8”

15.9mm

1/2”

12.7mm

40-100 feet

13-30 meters

1/2”

12.7mm

1/2”

12.7mm

3/4”

19mm

1/2”

12.7mm

100-150 feet

31-46 meters

3/4”

19mm

1/2”

12.7mm

7/8”

22.2mm

3/4”

19mm

Note: 

Never use plastic pipe. Check to confirm whether your local 

codes allow copper tubing or galvanized.

Note:

 Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:
—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 

and Fittings

—  ANS  Z21.45 Assembled  Flexible Appliance  Connectors  of 

Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority 
having jurisdiction. The state of Massachusetts requires that a flexible 
appliance connector cannot exceed three feet in length.

Figure 1  

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the 
unit. Where  none  exists,  or  where  its  size  or  location  is  not  ad-

equate, contact your local authorized installer for installation or 
relocation.

Compounds used on threaded joints of gas piping shall be resistant 
to the action of liquefied petroleum gases. The gas lines must be 
checked for leaks by the installer. This should be done with a soap 
solution watching for bubbles on all exposed connections, and if 
unexposed, a pressure test should be made. 

Never use an exposed flame to check for leaks. Appliance must 
be disconnected from piping at inlet of control valve and pipe 
capped or plugged for pressure test. Never pressure test with 
appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas 
line upstream of the gas control to aid in servicing. It is required 
by the National Fuel Gas Code that a drip line be installed near 
the gas inlet. This should consist of a vertical length of pipe tee 
connected into the gas line that is capped on the bottom in which 
condensation and foreign particles may collect.

Pressure Testing of the Gas Supply System

1.  To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. 

plugged tapping, accessible for test gauge connection, must be 
placed immediately upstream of the gas supply connection to 
the appliance.

2.  The  appliance  and  its  individual  shutoff  valve  must  be 

disconnected from the gas supply piping system during any 
pressure testing of that system at test pressures in excess of 
1/2 psig (3.5 kPa).

3.  The  appliance  must  be  isolated  from  the  gas  supply  piping 

system by closing its individual manual shutoff valve during 
any  pressure  testing  of  the  gas  supply  piping  system  at  test 
pressures equal to or less than 1/2 psig (3.5 kPa).

Attention! If anyone of the procedures results in pressures in 

excess of 1/2psig (14" w.c) (3.5kPa) on the fireplace gas valve, 
it will result in a hazardous condition.

Checking Maniflold Pressure

Both  propane  and  Natural  gas  valves  have  a  built-in  pressure 
regulatior in the gas valve. Natural gas models will have a valve 
outlet with the inlet pressure to the valve from a minimum of 5.0" 
w.c. (1.245kPa) for the purpose of input adjustment to a maximum 
of 10.5" w.c. (2.614kPa) Propane gas models will have a manifold 
pressure  apporximately  10.0"  w.s.  (2.49kPa)  at  the  valve  outlet 
with the inlet pressure to the valve from a minimum of 11.0" w.c. 
(2.739kPa)  for  the  purpose  of  input  adjustment  to  a  maxium  of 
13.0" w.c. (3.237kPa).

A  1/8"  (3mm)  N.P.T.  plugged  tapping,  accessible  for  test  gauge 
connection, is located on the outlet side of the gas control.

GAS SUPPLY

 ACF Greenhouses 

Summary of Contents for DV-55E

Page 1: ...his appliance is only for use with the type s of gas indicated on the rating plate A conver sion kit is supplied with the appliance Installer Leave this manual with the appli ance Consumer Retain this...

Page 2: ...assachusetts 5 Introduction 6 Specifications 6 Gas Supply 7 Gas Conversion Instructions 8 Clearances 9 Furnace Installation 9 11 Lighting Instructions 12 Wiring 13 Maintenance 14 Operation and Trouble...

Page 3: ...nstallation and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected beforeuseandatleastannuallybyaqualifiedserviceperson More frequent cleaning may be required due to...

Page 4: ...ights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption...

Page 5: ...naccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshall be permanently mounted to the exterior o...

Page 6: ...be performed only by a qualified agency The term qualified agency meansanyindividual firm corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible for a th...

Page 7: ...ontrol valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the g...

Page 8: ...ning Conversion must be done by a qualified service technician Main burner orifice s and new gas conversion label are provided in conversion kit attached to manifold pipe 1 Make sure gas supply to fur...

Page 9: ...NG The nearest point of the vent cap should be a minimum horizontal distant of six 6 feet 1 83m from any pressure regulator In case of regulator malfunction the six 6 feet 1 83m distance will reduce t...

Page 10: ...if plastic anchors are used Attach the two wall mounting brackets to the casing back by using 4 10 x 1 2 13mm hex head screws provided Figure 5 Figure 6 Figure 7 Figure 8 2 51mm TO 13 330mm 2 51mm TO...

Page 11: ...ach the right shroud and left shroud to the casing back the 3 4 wide flange on the shroud must be positioned toward the casing side When positioned correctly the 6 louvers on the shroud will be facing...

Page 12: ...lified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the therm...

Page 13: ...VAC circuit If current is below 1 micro amp remove sensor clean with light sandpaper and retest Note This heater is equipped with a remote bulb electronic thermistor control located down low at the ba...

Page 14: ...lve 4 Remove gas valve from gas valve bracket Removing Main Burner Orifice s 1 Remove front grill assembly 2 Remove burner compartment access panel 2 screws 3 Disconnect manifold union assembly 4 Disc...

Page 15: ...terminal on the board The inducer blower circuit is energized and the inducer blower comes on for 15 seconds pre purging out any gas and closing the pressure switch The hot surface ignitor is energize...

Page 16: ...essure switch is closed with inducer off Check Pressure Switch and Replace 4 Flashes Lockout due to failed ignition Check for Broken Ignitor Check for Bent Ignitor Bracket Ignitor too far from Burner...

Page 17: ...e Description of each part from the following appropriate illustration and list Be sure to give all this information Furnace Model Number Part Description Furnace Serial Number Part Number Type of Gas...

Page 18: ...19563 3 0907 Page 18 PARTS VIEW ACF Greenhouses...

Page 19: ...19563 3 0907 Page 19 SERVICE NOTES ACF Greenhouses...

Page 20: ...3 0907 Page 20 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com ACF Greenh...

Reviews: