background image

12431-10-1008

Page 9

Locating Wall Opening

The furnace is to be located on an outside wall. Locate wall studs so 

that wall opening will be located between wall studs. The furnace 

is 16 inches in width and normal 16 inches on center studs will 

not allow the furnace to be recessed into the wall unless a stud is 

repositioned.  The wall opening required as shown in Figure 5 is 

a diameter of 7 1/2 inches.
A template is provided in furnace carton for positioning furnace 

on the wall. Also, refer to Figure 5 for positioning the furnace on 

wall and for locating gas line connection.

Installing Optional Side Outlets

Side outlet register, SOR-1 may be installed on one or both sides 

of the furnace at the required clearances of 18 inches to adjacent 

wall or combustible material as shown in Figure 4. 

  1.  Locate and cut the 5 1/2" square opening in the cabinet side 

using the template from the kit, exposing the inner liner 

knock-out.

  2.  Remove the knock-out. 

  3.  Place the register on the 5 1/2" opening with the louvers set 

for the desired direction and mark the mounting holes using 

the register as a template. 

  4.  Drill (2) 1/8" diameter holes in cabinet side and fasten the 

register in place with (2) #10 x 1" screws provided. 

Side outlet kit, 10" boot assembly with register, SOK-1 for warm 

air discharge into an adjoining room may be installed on either side 

of the furnace at the required clearance of 4 inches to adjacent wall 

as shown in Figure 7. 
  1.  Locate and cut the 5 1/2" square opening in the cabinet side 

using the template from the kit, exposing the inner liner 

knock-out.

  2.  Remove the knock-out. 

  3.  Using the inner and outer boots as hole templates, mark and 

drill (8) 1/8" diameter holes in the inner liner and cabinet 

side.

  4.  Using Figure 7 locate and cut a 6 3/4" square opening through 

walls. 

  5.  Prepare wall opening for the vent-air intake system (see 

Locating Wall Opening

). 

  6.  With furnace in place, after checking alignment of side outlet 

opening in wall and furnace, place the 9 3/8" x 9 3/8" side 

outlet wall plate over outer boot, pass the outer boot through 

the wall and attach side outlet wall plate to furnace side of 

wall with (2) #10 x 1" screws provided. 

  7.  Fasten  outer  boot  to  the  cabinet  side  with  (4)  #8  x  1/4" 

screws provided. 

  8.  Position and attach inner boot to inner liner with (4) #8 x 

1/4" screws provided. 

  9.  Locate the register with its louvers positioned for the desired 

air discharge direction and mark the mounting holes using 

the register as a template. 

  10.  Drill (2) 1/8" diameter holes in the wall and fasten the register 

in place with (2) #10 x 1" screws provided.

Figure 5

 

 

Figure 6 

Figure 7

INSTALLATION INSTRUCTIONS

Summary of Contents for DV-55SPP

Page 1: ...se death or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other amma ble vapors and liquids in the v...

Page 2: ...tts 5 Introduction 6 Speci cations 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 S...

Page 3: ...appliance should be inspected before use and at least annually by a quali ed service person More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is imp...

Page 4: ...ghts perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption o...

Page 5: ...iredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certi ed 3 SIGNAGE Ametalorplasticidenti cationplateshallbe permanently mounted to the exterior...

Page 6: ...e by a moving vehicle Quali ed Installing Agency Installation and replacement of gas piping gas utilization equip ment or accessories and repair and servicing of equipment shall be performed only by a...

Page 7: ...e disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground...

Page 8: ...istance from the center of the vent cap to the nearest outside corner or obstruction is 24 inches The vent terminal of a direct vent appliance with an input over 50 000 BTU per hour shall be located a...

Page 9: ...0 x 1 screws provided Side outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 i...

Page 10: ...e mountingplate Useadditionalcaulkingtocorrectunevenwall surface such as clapboard 2 Remove old furnace cement from ue outlet collar on com bustion chamber and collar of vent cap Remove old furnace ce...

Page 11: ...it appears that a projection within 6 of any side of the air inlet section could shield the air inlet section the entire vent should be supported away from the wall at least the distance of the projec...

Page 12: ...ectric power to the appliance 15 Set thermostat to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a re or explosion may result causing pro...

Page 13: ...ing the burner door from the combustion chamber remove rear burner pilot burner and front burner With front and rear burners removed from furnace force water into the ribbon ports and dry with air pr...

Page 14: ...ing can be purchased plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can bepluggedintotheada...

Page 15: ...rnace is rst installed or was off all summer the pilot ame may be too lean to ignite on the rst few trials Turn the controlvalveknobtopilotpositionanddepresstheredresetbutton Holding the button down c...

Page 16: ...Gasket for Burner Door 40 722040 Manifold Union 41 R 5655 Gas Valve VR8200C LP Gas 41 R 2148 Gas Valve VR8200C Natural Gas 42 UH 810 Transformer Mounting Bracket 43 R 1995 Transformer 44 UH 451 Juncti...

Page 17: ...12431 10 1008 Page 17 PARTS VIEW...

Page 18: ...12431 10 1008 Page 18 SERVICE NOTES...

Page 19: ...12431 10 1008 Page 19 SERVICE NOTES...

Page 20: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: