40946-0-1019

Page 8

GAS SUPPLY

Locating Gas Supply

The gas line can enter the unit either through the floor or outside 

wall.  The gas line opening should be made at this time.  Location 

of the opening will be determined by the position of floor joists and 

the valve and union used for servicing.

RECOMMENDED GAS PIPE DIAMETER

Pipe 

Length

Schedule 40 Pipe

Inside Diameter

Tubing, Type L 

Outside Diameter

Natural

Propane

Natural

Propane

0-10 feet

0-3 meters

1/2”

12.7 mm

3/8”

9.5mm

1/2”

12.7 mm

3/8”

9.5 mm

10-40 feet

4-12 meters

1/2”

12.7 mm

1/2”

12.7mm

5/8”

15.9 mm

1/2”

12.7 mm

40-100 feet

13-30 meters

1/2”

12.7 mm

1/2”

12.7mm

3/4”

19 mm

1/2”

12.7 mm

100-150 feet

31-46 meters

3/4”

19 mm

1/2”

12.7 mm

7/8”

22.2 mm

3/4”

19 mm

NOTE:

 Never use plastic pipe. Check to confirm whether your local 

codes allow copper tubing or galvanized.

NOTE: 

Since some municipalities have additional local codes, it 

is always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:

—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 

and Fittings

—  ANS Z21.45 Assembled Flexible Appliance Connectors of Other 

Than All-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The Commonwealth of Massachusetts requires 

that a flexible appliance connector cannot exceed three feet in length.

NPT NIPPLE

Figure 1 

Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/

CGA-B149 (.1 or .2) installation code. 

Installing a New Main Gas Shut-Off

Each appliance should have its own manual gas shut-off.

A manual main gas shut-off should be located in the vicinity of the 

unit. Where none exists, or where its size or location is not adequate, 

contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

Never use an exposed flame to check for leaks. Appliance must be 

disconnected from piping at inlet of control valve  and pipe capped 

or plugged for pressure test. Never pressure test with appliance 

connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required by 

the National Fuel Gas Code that a drip line be installed near the gas 

inlet. This should consist of a vertical length of pipe tee connected 

into the gas line that is capped on the bottom in which condensation 

and foreign particles may collect. 

Figure 2

Method of Installing a Tee Fitting Sediment Trap

Pressure Testing of the Gas Supply System

1.  To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. 

plugged tapping, accessible for test gauge connection, must be 

placed immediately upstream of the gas supply connection to 

the appliance.

2.  The appliance and its individual shut-off valve must be 

disconnected from the gas supply piping system during any 

pressure testing of that system at test pressures in excess of 

1/2 psig (3.5 kPa).

3.    The appliance must be isolated from the gas supply piping system 

by closing its individual manual shut-off valve during any pressure 

testing of the gas supply piping system at test pressures equal 

to or less than 1/2 psig (3.5 kPa).

Attention!

 If one of the above procedures results in pressures 

in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas 

valve, it will result in a hazardous condition.

Checking Manifold Pressure

Both Propane and Natural Gas valves have a built-in pressure 

regulator in the gas valve. Natural Gas models will have a manifold 

pressure of approximately 4.0" w.c. (.996kPa) at the valve outlet 

with the inlet pressure to the valve from a minimum of 5.0" w.c. 

(1.245kPa) for the purpose of input adjustment to a maximum of 

10.5" w.c. (2.61kPa). Propane Gas models will have a manifold 

pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet 

with the inlet pressure to the valve from a minimum of 11.0" w.c. 

(2.739kPa) for the purpose of input adjustment to a maximum of 

13.0" w.c. (3.237kPa). 

A 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge 

connection, is located on the outlet side of the gas control.

Summary of Contents for DV210SGXLP-2

Page 1: ...try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas supplier from a neighbor s phone Follow the...

Page 2: ...Specifications 6 Gas Supply 7 Clearances 8 Installation Instructions 8 9 Lighting Instructions 10 Maintenance 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Troubleshooting 13...

Page 3: ...a qualified service person More frequent cleaning may be required due to ex cessive lint from carpeting bedding materials etc It is imperative that control compartments burners and circulating air pas...

Page 4: ...adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity Propane Gas may stratify in a closed...

Page 5: ...ide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be per...

Page 6: ...g of equipment shall be performed only by a qualified agency The term qualified agency means any individual firm corporation or company which either in personorthrougharepresentativeisengagedinandisre...

Page 7: ...n while all other appliances connected to the venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as...

Page 8: ...test should be made Never use an exposed flame to check for leaks Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test...

Page 9: ...m screw provided On sheet rock wall secure furnace support bracket with 1 toggle bolt provided 64mm 13mm Figure 4 INSTALLATION INSTRUCTIONS 1 In selecting a location for installation it is necessary t...

Page 10: ...side wall plate Use additional caulking to correct uneven wall surface such as clapboard 3 Attach 5 127mm diameter air inlet tube onto the collar of air drop assembly Attach caulked outside wall plate...

Page 11: ...ockwise to ON 12 Replace control access panel front panel 13 Turn on all electric power to the appliance if applicable 14 CAUTION Pilot access cover must be kept tightly closed during operation TO TUR...

Page 12: ...orifice threads when replaced 5 To remove the entire gas valve the nut holding the orifice fitting to the chamber must be removed and the gas supply to the valve disconnected After this the valve and...

Page 13: ...Replace 3 Yellow pilot flame a Obstruction at pilot orifice b Clean and properly size orifice 4 Pilot and main burner go out during normal operation a Check millivolts b Check for proper size of pilot...

Page 14: ...P8658 BURNER ORIFICE DV215 PROPANE 13 P104 ORIFICE FITTING 14 R1055 ELECTRODE AND WIRE 15 R12797 MANIFOLD 16 R12791 GAS VALVE 7000 MVRLC NATURAL 16 R12792 GAS VALVE 7000 MVRLC PROPANE 17 R12795 PILOT...

Page 15: ...40946 0 1019 Page 15 MODEL DV 210 SHOWN 1 2 3 4 5 6 7 8 9 10 13 12 17 11 18 19 14 15 21 20 16 22 23 25 24 26 27 31 28 29 30 PARTS VIEW MODEL DV 210 SHOWN...

Page 16: ...bsence of local codes with the National Electrical Code ANSI NFPA 70 or Canadian Electrical Code CSA C22 1 if an external electrical source is utilized This appliance is equipped with a three prong gr...

Page 17: ...l Furnaces DV210 and DV215 OPTIONAL BLOWER INSTALLATION INSTRUCTIONS Oiling the Motor Oiling holes are provided on each end of the motor for oiling The blower should have five drops of 20 motor oil ev...

Page 18: ...se and can be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model...

Page 19: ...le cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might result from t...

Page 20: ...ww empirecomfort com Empire Comfort Systems Inc Belleville IL If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question plea...

Page 21: ...endido 9 DV 781 Ensamblaje Cubierta Agujero Encendido 10 DV 064 L mina Cubierta Agujero Encendido 11 852098 Tuerca para Tenedor Inyector 12 742134 Inyector Quemador DV 210 Natural 12 742133 Inyector Q...

Page 22: ...40946 0 1019 Page 17 VISTA DE PARTES MODEL DV 210 SHOWN 1 2 3 4 5 6 7 8 9 10 13 12 17 11 18 19 14 15 21 20 16 22 23 25 24 26 27 31 28 29 30 MODELO DV 210 MOSTRADO...

Page 23: ...ran los c digos locales de protecci n CUIDADO Marque todos los cables antes de la conexi n cuando le d servicio a los controles Errores atribuidos a conexi n de cables pueden causar una operaci n inco...

Page 24: ...con el artefacto Se debe conservar un comprobante de venta un cheque cancelado o un registro de pago para verificar la fecha de compra y establecer el per odo de garant a Acceso f cil al artefacto par...

Page 25: ...Comfort Systems Inc Belleville Illinois Si Ud tiene una pregunta general acerca de nuestros productos por favor env enos un correo al info empirecomfort com Si Ud tiene una pregunta de servicio o de r...

Reviews: