Page 7

32188-0-0616

GAS SUPPLY

Locating Gas Supply

The gas line can enter the unit either through the floor or outside 

wall.  The gas line opening should be made at this time.  Location 

of the opening will be determined by the position of floor joists and 

the valve and union used for servicing.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Inside Diameter

Tubing, Type L 

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10 feet

0-3 meters

1/2”

12.7 mm

3/8”

9.5mm

1/2”

12.7 mm

3/8”

9.5 mm

10-40 feet

4-12 meters

1/2”

12.7 mm

1/2”

12.7mm

5/8”

15.9 mm

1/2”

12.7 mm

40-100 feet

13-30 meters

1/2”

12.7 mm

1/2”

12.7mm

3/4”

19 mm

1/2”

12.7 mm

100-150 feet

31-46 meters

3/4”

19 mm

1/2”

12.7 mm

7/8”

22.2 mm

3/4”

19 mm

Note:

 Never use plastic pipe. Check to confirm whether your local 

codes allow copper tubing or galvanized.

Note: 

Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:

—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 

and Fittings

—  ANS Z21.45 Assembled Flexible Appliance Connectors of Other 

Than all-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The state of Massachusetts requires that a 

flexible appliance connector cannot exceed three feet in length.

NPT NIPPLE

Figure 1 

Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/

CGA-B149 (.1 or .2) installation code. 

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. 

Where none exists, or where its size or location is not adequate, 

contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. 

The gas lines must be checked for leaks by the installer. This should 

be done with a soap solution watching for bubbles on all exposed 

connections, and if unexposed, a pressure test should be made. 

never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve  and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!

a gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required by 

the National Fuel Gas Code that a drip line be installed near the gas 

inlet. This should consist of a vertical length of pipe tee connected 

into the gas line that is capped on the bottom in which condensation 

and foreign particles may collect. 

Figure 2 

Method of Installing a Tee Fitting Sediment Trap

Pressure Testing of the Gas Supply System

1.  To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. 

plugged tapping, accessible for test gauge connection, must be 

placed immediately upstream of the gas supply connection to 

the appliance.

2.  The appliance and its individual shutoff valve must be 

disconnected from the gas supply piping system during any 

pressure testing of that system at test pressures in excess of 

1/2 psig (3.5 kPa).

3.    The appliance must be isolated from the gas supply piping system 

by closing its individual manual shutoff valve during any pressure 

testing of the gas supply piping system at test pressures equal 

to or less than 1/2 psig (3.5 kPa).

Attention! 

If one of the above procedures results in pressures in 

excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, 

it will result in a hazardous condition.

Figure 3

Summary of Contents for DVC55SPPXLP-1

Page 1: ...combustion which can cause death or serious illness Installer Leave this manual with the appliance Consumer Retain this manual for future reference WARNING If the information in these instructions ar...

Page 2: ...duction 6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and...

Page 3: ...The appliance should be inspected before use and at least annually by a qualified service person More frequent cleaning may be required due to excessive lint from carpet ing bedding materials etc It i...

Page 4: ...gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clo...

Page 5: ...oxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be pe...

Page 6: ...ied Installing Agency Installation and replacement of gas piping gas utilization equip ment or accessories and repair and servicing of equipment shall be performed only by a qualified agency The term...

Page 7: ...local authorized installer for installation or relocation Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases The gas lines must be checked f...

Page 8: ...distance from the center of the vent cap to the nearest outside corner or obstruction is 24 inches CLEARANCES Checking Manifold Pressure Both Propane and Natural gas valves have a built in pressure re...

Page 9: ...provided Side outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adj...

Page 10: ...ove old furnace cement from both ends of 4 diameter flue outlet tube 3 Attach 6 diameter air inlet tube onto the collar of air drop assembly Attach caulked outside mounting plate into the 6 diameter a...

Page 11: ...e projection 2 x 4 framing whose outside dimensions match the overall dimensions of the mounting plate is recommended The 2 x 4 framing protects siding from possible warpage or discoloration All joint...

Page 12: ...power to the appliance FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of l...

Page 13: ...emovingthe burner door from the combustion chamber remove rear burner pilot burner and front burner With front and rear burners removed from furnace force water into the ribbon ports and dry with air...

Page 14: ...toggle switch or thermostat remove the wire nut from the two wires from the valve Run additional wire from the valve wires to the ON OFF device Install the ON OFF device in the same room as the furnac...

Page 15: ...r Does Not Light Pilot With air in the gas line such as when the furnace is first installed or was off all summer the pilot flame may be too lean to ignite on the first few trials Turn the control val...

Page 16: ...l Gas 28 DV808 Pilot Tubing 29 DV824 Front Burner 30 P8842 Main Burner Orifice Natural Gas Two Required 30 P8853 Main Burner Orifice LP Gas Two Required 31 DV687 Manifold and Plate Assembly 32 M148 Ma...

Page 17: ...Page 17 32188 0 0616 PARTS VIEW...

Page 18: ...ranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numb...

Page 19: ...le cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might result from t...

Page 20: ...mfort Systems Empire Comfort Systems Inc Belleville IL If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please cont...

Page 21: ...rieuses maladies Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables dans le voisnage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE...

Page 22: ...st chaud lorsque le radiateur est en fonction L installation et la r paration doivent tre faites par une per sonne qualifi e L appareil doit tre inspect avant l usage et au moins une fois par ann e pa...

Page 23: ...bas Attendez que les pompiers vous assurent de la s ret de ces endroits avant d y aller Utiliser le t l phone de votre voisin et appeler les pompiers et une personne entra n e avec le propane Ne pas...

Page 24: ...e gaz d entrer par le capuchon de l vent Emplacement de l Ouverture dans le Mur Le radiateur doit tre situ sur un mur ext rieur Trouver les montants du mur ainsi l ouverture dans le mur sera entre les...

Page 25: ...d espace libre aux mat riaux combus tibles venant du d gage ment du registre de chaque c t Entr e de gaz Enlever plinthe et moulure ouverture d vent 7 1 2 19cm Mur ar ri re Minimum d espace libre au c...

Page 26: ...l entr e de la pluie Attacher la plaque ext rieure de montage au mur ext rieur avec 4 vis 10 x 1 38mm Les vis sont fournies 4 Appliquer du ciment pour radiateur au collet de la sortie Emplacement de l...

Page 27: ...ourrev tementnedoitpasexc derune paisseur totale de 13 33 02cm pour le DV 55 voir Figure 5a AVERTISSEMENT Lorsque l ensemble d vent pour le rev tementenvinyleDV 822oulaconstructionfaitede2 x 4 5 08cm...

Page 28: ...x et de raccords en m tal ondul ANS Z21 45 Connexions flexibles d appareil autre qu en m tal Les connexions ci dessus peuvent tre utilis es si elles sont accept es par les autorit s ayant juridiction...

Page 29: ...index no 4 pi ce no 712059 Les joints d tanch it doivent tre tir s pour s adapter sur les boulons du moteur dans les espaces pour joint d tanch it Le moteur et les joints d tanch it peuvent tre insta...

Page 30: ...tournerle bouton de contr le de gaz N utiliserjamais des outils Si vousnepouvezpaspousseroutournerleboutonavecvos mains n essayerpasdeler parer appeleruntechnicien qualifi Forcer ou essayer de r parer...

Page 31: ...a veilleuse et r allumer La veilleuse s enflamme mais s teint lorsque le bouton est rel ch 1 Suivre les instructions et appuyer sur le bouton plus long temps et fermement 2 D terminer si la flamme de...

Page 32: ...semblage du br leur avant 30 P8842 Br leur principal avec ouverture gaz naturel exige deux 30 P8853 Br leur principal avec ouverture gaz propane exige deux 31 DV687 Tuyau de gaz et assemblage de plaqu...

Page 33: ...Page 13 32188 0 0616 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 2623...

Page 34: ...aiement pour attester de la date d achat et tablir la p riode de garantie Acc s imm diat l appareil pour la r paration Ce qui n est pas couvert Dommages pouvant r sulter de l emploi de l emploi abusif...

Page 35: ...Page 15 32188 0 0616 NOTES DE SERVICE...

Page 36: ...ire Comfort Systems Inc Belleville IL Pour toute question g n rale concernant nos produits veuillez nous envoyer un courriel info empirecomfort com Pour toute question d entretien ou de r paration veu...

Reviews: