background image

Figure 2

GAS SUPPLY

Compounds used on threaded joints of gas piping shall be 
resistant to the action of liquefied petroleum gases. The gas 
lines must be checked for leaks by the installer. This should be 
done with a soap solution watching for bubbles on all exposed 
connections, and if unexposed, a pressure test should be made. 

A gas valve and ground joint union should be installed in the 
gas line upstream of the gas control to aid in servicing. It is 
required by the National Fuel Gas Code that a drip line be 
installed near the gas inlet. This should consist of a vertical 
length of pipe tee connected into the gas line that is capped on 
the bottom in which condensation and foreign particles may 
collect.

Never use an exposed flame to check for leaks. Appliance 
must be disconnected from piping at inlet of control valve 
and pipe capped or plugged for pressure test. Never 
pressure test with the appliance connected; control valve 
will sustain damage!

Pressure Testing of the Gas Supply System

Attention! 

Checking Manifold Pressure

1. To check the inlet pressure to the gas valve, a 1/8" (3 mm) 

N.P.T. plugged tapping, accessible for test gauge 
connection, must be placed immediately upstream of the 
gas supply connection to the appliance.

2. The appliance and its individual shutoff valve must be 

disconnected from the gas supply piping system during any 
pressure testing of that system at test pressures in excess of 
1/2 psig (3.5 kPa).

3. The appliance must be isolated from the gas supply piping 

system by closing its individual manual shutoff valve 
during any pressure testing of the gas supply piping system 
at test pressures equal to or less than 1/2 psig (3.5 kPa).

If one of the above procedures results in pressures 

in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas 
valve, it will result in a hazardous condition.

Both Propane and Natural gas valves have a built-in pressure 
regulator in the gas valve. Natural gas models will have a 
manifold pressure of approximately 4.0" w.c.(.996kPa) at the 
valve outlet with the inlet pressure to the valve from a 
minimum of 5.0" w.c.(1.245kPa) for the purpose of input 
adjustment to a maximum of 10.5" w.c.(2.61kPa). Propane gas 
models will have a manifold pressure approximately 10.0" 
w.c.(2.49kPa) at the valve outlet with the inlet pressure to the 
valve from a minimum of 11.0" w.c.(2.739kPa) for the purpose 
of input adjustment to a maximum of 13.0" w.c.(3.237kPa). A 
1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge 
connection, is located on the outlet side of the gas control.

Locating Gas Supply

Recommended Gas Pipe Diameter

Note: 

Note: 

The gas line can enter the unit either through the floor or 
outside wall. The gas line opening should be made at this time. 
Location of the opening will be determined by the position of 
floor joists and the valve and union used for servicing.

Never use plastic pipe. Check to confirm whether your 

local codes allow copper tubing or galvanized.

Since some municipalities have additional local codes, 

it is always best to consult your local authority and installation 
code.

The use of the following gas connectors is recommended:

— ANS Z21.24 Appliance Connectors of Corrugated Metal 

Tubing and Fittings

— ANS Z21.45 Assembled Flexible Appliance Connectors of 

Other Than All-Metal Construction

The above connectors may be used if acceptable by the 
authority having jurisdiction. The state of Massachusetts 
requires that a flexible appliance connector cannot exceed 
three feet in length.

Consult the current National Fuel Gas Code, ANSI Z223.1 
CAN/CGA-B149 (.1 or .2) installation code.

Each appliance should have its own manual gas cock. In the 
state of Massachusetts the gas cock must be a T handle type. A 
manual main gas cock should be located in the vicinity of the 
unit. Where none exists, or where its size or location is not 
adequate, contact your local authorized installer for 
installation or relocation.

Installing a New Main Gas Cock

Pipe Lenght

(Feet)

Schedule 40 Pipe

Inside Diameter

Tubing, Type L

Outside Diameter

Nat.
1/2”

1.3 cm

5/8”

1.6 cm

3/4”

1.9 cm

7/8”

2.2 cm

L.P.

3/8”

1.0 cm

1/2”

1.3 cm

1/2”

1.3 cm

3/4”

1.9 cm

0 - 10

10 - 40

40 - 100

100 - 150

Figure 1

3” (76 mm)

DRIP LEG

Alternate locations 

for shut off valve

Gas supply inlet

NPT Niple

NPT Niple

Close Niple

Shut Off

Valve

NPT Gas 

Supply

NPT Union

Flare Fitting

Flex 

Tubbing

Flare Shut 

Off Valve

Gas 

Supply

Tee 

Handle

Tee Handle

FLEXIBLE GAS LINE CONNECTION

RIGID GAS LINE CONNECTION

Page 6

L.P.

3/8”

1.0 cm

1/2”

1.3 cm

1/2”

1.3 cm

1/2”

1.3 cm

Nat.
1/2”

1.3 cm

1/2”

1.3 cm

1/2”

1.3 cm

3/4”

1.9 cm

MV1XX-1-0603

Summary of Contents for MV 120

Page 1: ...ng Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier callthe fire department Installation and service must be performed by a qualified installer service agencyor thegassupplier This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other ga...

Page 2: ...duction Specifications Gas Supply Clearances Installation Instructions Lighting Instructions Pilot Flame Characteristics Main Burner Flame Characteristics Maintenance How to Order Repair Parts Parts List Parts View Troubleshooting PAGE 3 4 5 5 6 7 8 8 10 11 12 12 12 13 13 14 15 16 Page 2 MV1XX 1 0603 ...

Page 3: ... e n q u e e s t á i n s t al a d o e l a p a r a t o L a r o p au o t r o s m a t e r i a l e s i n f l a m a b l e s n o d e b e n c o l o c a r s e e n ci m a o c e r c a d e e s t e a p a r a t o C u a l q u i e rp a n t a l l a d e s e g u r i d a d o pa n e l q u e s e a r e t i r a d o p a r a r e a l i z a re l s e r v i c i o d e l e q u i p o de b e s e r r e i n s t a l a d o a n t e s ...

Page 4: ...odorlessand colorless You may not know all the following safety pre cautions which can protect both you and your family from an accident Read them carefully now then review them point by point with the members of your household Do not operate electric switches light matches use your phone Donotdoanythingthatcouldignitethegas Get everyone out of the building or area Do that IMMEDIATELY Closeall gas...

Page 5: ... Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shownontherating plate is theresponsibility of theperson andcompanymakingthechange Important Notice Always consult your local Building Department regarding regulations codes or ordinances which apply to the installation of adirectventwallfurnace 1 Installer must leave instructio...

Page 6: ...2 61kPa Propanegas models will have a manifold pressure approximately 10 0 w c 2 49kPa at the valve outlet with the inlet pressure to the valvefromaminimumof11 0 w c 2 739kPa forthepurpose of input adjustment to a maximum of 13 0 w c 3 237kPa A 1 8 3mm N P T plugged tapping accessible for test gauge connection islocatedontheoutletside ofthegascontrol LocatingGas Supply Recommended Gas Pipe Diamete...

Page 7: ...nter of theventcaptothe nearestoutsidecornerorobstruction is 16 407mm 5 The MV 120 MV 130 and MV 145 minimum wall depth is 4 1 2 114 mm and the maximum is 12 305 mm The Figure 3 Vent terminal clearances A A G C F L D E B A B C D E F G H I clearance above grade veranda porch deck or balcony clearance to window or door that may be opened clearance to permanently closed window vertical clearance to v...

Page 8: ...nttheunittobemounted A full scale template is furnished with the unit which illustrates the vent and gas supply openings and mounting holesintheir correctlocationsonthewall the figure 4 gives the required dimensions for mounting theunit intheeventthatthe templateisunusableorlost Place the template on the wall so that the vent opening will be located between the studs and in the case of the MV 130 ...

Page 9: ...comes through the wall It is not where you willcutthepipes It is very important that this be a clean straight cut for the heatertoperformproperly Remember to remove the vent assembly from the wall in ordertocut thetubes Installingtheventassemblyandwallsupportplate the indicated diameter in both walls and cut them Your hole will be about 1 to 2 26 to 52 mm depending on the unit model larger indiame...

Page 10: ...valve or at the gas meter or propane LPtankserving thebuilding Fixtheleaking jointand re testthejoints as directedabove Once the supply is checked and does not leak place the cover on the unit See Figure 10 Be sure the foam packing has been removed Secure the cover with the two nuts at the bottom of theunitwhich youhadremovedwhenunpacking eventualwaterfiltrationortheentranceofbugsisnecessary Press...

Page 11: ...he gas control knob counter clockwise to the PILOT position Depress the gas control knob and push in the Piezo igniter several times until the pilot is lit The pilot flame can be observed by looking down the inside of the heater jacket A small reflector on the right hand side near 1 Setthethermostatto lowestsetting 2 Openthe controlaccess panelonthetop rightside oftheunit 3 Turn the gas knob clock...

Page 12: ...in thesupplypipingleading to theappliance ifinstalled or at the gas meter or propane LP tank 3 Remove the two screws which hold the unit to the wall supportplateandliftandpulltheunitawayfromthewall 4 Carefully examine the interior of the vent pipes both large and small diameter If you notice any blockage or obstruction cleanthepipes 5 Look insidetheopenings of the rear oftheunitandcheckfor any for...

Page 13: ...ine with a soapy water solution Bubbles on any of the joints indicated a leak is present and must be repaired Turn OFF the gas to the unit when performing any repairs to the gas piping system After the pilot lines are checked turn the main burner ON and again check all joints in the piping system for leaks with soapy water Repair any joints which indicate a leak ispresent 12 While the main burner ...

Page 14: ...43018500 SD430185B0 SD442202B0 SK00000048 SK00000051 SD44107500 SD44105800 SD44305500 SD44177000 SD44176900 SD44175800 SD44120800 SA00000263 SD44107002 SD44107100 SD44106900 SD44106801 SK00000053 SK00000054 SD44106100 SD44158001 SD44158102 SD44125500 SD44125200 SD443332C0 SD443332D0 SD44111300 SD44132400 SD44152900 SD44153000 SK00000055 PART MV 145 N SD43018400 SD430184B0 SD44326100 SK00000049 SK0...

Page 15: ...Page 15 PARTS VIEW MV1XX 1 0603 ...

Page 16: ...ning thesmallbrassscrewonthelefthand fronttop of the gas control top plate Backing the screw out counterclockwise increases the pilot flame The pilot flame should contact the thermocouple tip but not excessively long SeeLightingInstructions the thermocouple is a standard 24 millivolt probe Check its effectiveness by removing it from the heater and attach a probe alligator clip to themagnetcontactb...

Reviews: