Select a location with adequate accessibility clearances for servicing
and proper installation. Locate the wall furnace within 5 feet of a 115
VAC wall receptacle to properly power the wall furnace. Do
NOT
use an extension cord.
When facing the front of the wall furnace the minimum clearances
from casing to combustible construction are 12" (305mm) on top, 0"
(0mm) on each side and 0” (0mm) from the floor, 0” (0mm) to rear
wall, and 36” (914mm) in front of the wall furnace to walls or furniture.
Notice:
It is recommend to leave 8" (203mm) clearance on each
side for servicing, furniture and other easily moved items may be
placed to the sides (not the front) of the wall furnace.
See Figure 23.
CLEARANCES TO COMBUSTIBLES
INTRODUCTION
12”
0”
(8” service area
recommended)
36”
0”
(8” service area
recommended)
Figure 23