37873-0-0217
Page 26
VENTING REQUIREMENTS
WALL FURNACE INSTALLATION
WARNING
This appliance must not be vented with any other applianc
-
es, even if that appliance is of the condensing type. Com
-
mon venting can result in severe corrosion of other appli
-
ances or their venting and can allow combustion gases to
escape through such appliances or vents. Do not vent the
wall furnace into a fireplace chimney or building chase. The
flue exhaust pipe must be vented outside.
WARNING
Upon completion of the installation, carefully inspect the en
-
tire flue system to ensure it is properly sealed. DO NOT use
any vent material other than what is specified in this manual.
Leaks in the flue system can result in serious personal injury
or death due to exposure of flue products, including carbon
monoxide.
The UltraSaver is classified as a “Category IV” appliance, which
requires special venting materials and installation procedures.
Installations can be Conventional (one-pipe) and Direct Vent
(two-pipe). Venting must be completed with 1-1/2 or 2 inch diam-
eter pipe. In selecting a location for installation, it is necessary to
provide adequate clearances for servicing and proper installation.
All vent and combustion air pipes and fittings must be Schedule
40 PVC, ULC S636 and meet the ANSI/ASTM Standard D1785.
Cement must conform to ASTM Standard D2564.
Installation in Canada must conform to the requirements of CSA
B149 code. Vent systems must be composed of pipe, fittings,
cements, and primers listed to ULC S636. In Canada, the primer
and cement must be of the same manufacturer as the vent
system; do not mix primers and cements from one manufacturer
with a vent system from a different manufacturer. Follow the
manufacturer’s instructions the use of primer and cement and
never use primer or cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent system
is based on following these installation instructions, the vent
system manufacturer’s installation instructions, and proper use
of primer and cement. Acceptability under Canadian standard
CSA B149 is dependent upon full compliance with all installation
instructions. Under this standard, it is recommended that the vent
system be checked once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be
consulted before installation to determine the need to obtain a
permit.
The maximum vent length is 40 feet equivalent with (3) 90°
elbows.
The minimum vent length is 12 inches.
Each 90°
elbow used in the vent system will be the equivalent to 3 feet,
and each 45° elbow is equivalent to 1.5 feet, which should be
added to the overall vent length.
1. The installation must conform with, as applicable:
A. A non-metallic venting system for use in Canada shall
be listed to the Standard for Type BH Gas Venting
Systems, ULC S636.
B. A maintenance schedule, when a means is provided to
neutralize condensate, if required.
C. Periodic cleaning of the condensate collection and
disposal system(s), if required.
D. For Category IV appliances:
(1) When the manufacturer supplies the venting
system, the instructions shall include a parts list
and instructions covering the installation of properly
identified parts to provide for the venting of the vent
gases to the outdoors.
(2) When the parts for venting the vent gases are not
provided by the manufacturer and they are specific
types listed by a nationally recognized testing
agency, these instructions shall clearly identify and
specify the use of the specific parts.
2. For Category IV appliances, the venting system shall be
installed in accordance with the appliance manufacturer’s
instructions.
3. Instructions for proper venting installation:
A. Horizontal portions of the venting system shall:
(1) Be supported to prevent sagging. The methods of
and intervals for supports shall be specified in the
installation manuals.
(2) Slope upwards not less than 1/4 in/ft (21 mm/m)
from the appliance to the vent terminal.
(3) Category IV appliances shall be installed so as to
prevent accumulation of condensate in the venting
system.
4. Category IV appliance installations shall provide a means for
removal of condensate.
5. For appliance installation instructions accompanying a direct
vent appliance or other appliance that can utilize a side wall
vent system shall include information on where the vent
terminal can and cannot terminate, including:
For Category IV appliances, the following statement:
The vent for this appliance shall not terminate:
(a) Over public walkways; or
(b) Near soffit vents or crawl space vents or other
areas where condensate or vapor could create a
nuisance or hazard or cause property damage; or
(c) Where condensate vapor could cause damage or
could be detrimental to the operation of regulators,
relief valves, or other equipment.
6. Non-metallic venting systems shall not interchange
components with another listed or unlisted metallic or
nonmetallic vent systems.
Attention: Check local codes for venting requirements.
NOTE:
IPEX System 636 Flue Gas Venting Adaptor is provided.
Installer to check for adhesive material requirements.
Empire approved poly pipe with gasketed joints may also be used.
Contact your Empire dealer for availability. The use of vent tubes
not approved by the manufacturer may result in unsatisfactory per-
formance.
Summary of Contents for PVS18N-3
Page 7: ...37873 0 0217 Page 7 OWNER S MANUAL AND OPERATION INSTRUCTIONS www empirezoneheat com...
Page 13: ...37873 0 0217 Page 13 INSTALLATION INSTRUCTIONS www empirezoneheat com...
Page 55: ...37873 0 0217 Page 7 GUIDE D UTILISATION ET INSTRUCTIONS D INSTALLATION www empirezoneheat com...
Page 61: ...37873 0 0217 Page 13 INSTRUCTIONS D INSTALLATION www empirezoneheat com...