background image

33675-2-0219

Page 2

Empire Comfort Systems Inc. • Belleville, Illinois

Gas input for counterflow wall furnace converted to 

natural gas:

 

•  DVC55SPPX-1

 ...............

55,000 BTU per hour

•  DV551SPP

 .....................

55,000 BTU per hour

•  FAW551SPP

 ..................

55,000 BTU per hour

•  FAW55SPPX-1

 ...............

55,000 BTU per hour

The 

dV55-1spp

 and the 

Faw55-1spp

 wall furnaces when 

converted to Natural Gas will have manifold pressure of 4.0” 

w.c. at the valve outlet with the inlet pressure to the valve 

from a minimum of 5.0” w.c., for the purpose of input adjust-

ment, to a maximum of 10.5” w.c.

iNsTruCTioNs For CoNVErsioN

1.  If unit is installed, turn off gas and electric supply before 

making conversion.

2.  Remove thermocouple and pilot tubing from gas valve. 

Disconnect gas line at gas valve.

3.  Remove the eight (8) screws holding the burner assem-

bly to the combustion chamber and the two (2) screws 

holding the manifold bracket to the control compartment 

divider panel. Remove the complete burner assembly.

4.  Remove the rear burner from the burner assembly.
5.  Remove the pilot tubing from the pilot and replace the 

pilot orifice with the pilot orifice

 marked .018

 supplied in 

conversion kit.

6.  Replace the pilot tubing onto the pilot. 
7.  Replace rear burner to burner assembly.
8.  Remove  main  burner  orifices  and  replace  with  main 

burner orifices 

marked 42 

supplied in conversion kit. 

9.  Remove gas valve and replace with gas valve 

marked 

4.0, Vr8200C1165

 supplied in conversion kit.

10. Attach thermocouple and pilot tubing to gas valve.
11.  Replace  and  attach  complete  burner  assembly  into 

combustion chamber with screws removed in Step 3.

12. Attach gas line to gas valve.
13. The converted furnace must be connected to a supply 

of the conversion gas and checked for leaks.

14. The furnace must be checked to ensure it is operating 

at the correct pressure of 4.0” w.c.

The burner flame and pilot flame must also be checked 

for proper flame characteristics as outlined in installa-

tion instructions and owner’s manual.

Verifying input rate of Converted Furnace

The input of this furnace must be checked as follows: 

1.  Turn off all other gas appliances. Clock the gas meter 

and determine the number of seconds required to con

-

sume one cubic foot of gas.

2.  3600 ÷ time (in seconds) = cu. ft. per hour.
3.  Then cu. ft. per hour x heating value of gas = input rate 

(BTUH). On installation without gas meters, check man-

ifold for proper pressure.

placement of Conversion Label

1.  Conversion label R-1322 is to be placed in a location 

visible when all heater panels are installed.

If furnace is not installed or warranty card has not been re-

turned to Empire Comfort Systems, Inc., check off type of 

gas converted to on card. Also, indicate conversion by add-

ing “Conv.” behind gas.