background image

37134-4-0319

Page 11

SErVIcE AND MAINTENANcE SuGGESTIoNS

cALL SERVIcEMAN

GENErAl: 

All furnaces have been fire-tested to check for proper 

operation. This includes, main burner flame, pilot flame, fan operation, 

fan control, limit control and valve operation. If the furnace fails to 

function on initial installation, it is advisable to re-check the following: 

1. 115 volts to the junction box.

2. Inlet gas pressure.

3. The 24 volt system.

4. Type of gas being used and that shown on the rating label.

Standing Pilot Model

Servicing the Pilot and Main Burners, Pilot orifice, Thermo

-

couple, and Main Burner orifices: 

Disconnect the gas supply at 

the inlet to the control valve. Then remove the burner door to gain 

access to the above listed components.

If Electrode Does Not Produce Spark:

1.  check wire connections.

2.  check gap for pilot burner to the electrode tip. Should be between 

1/8" (3mm) and 3/16" (5mm). Electrode wire and tip must be 

more than 1/4" (6mm) away from all other metal components.

If Pilot Does Not light By Any Means:

1.  check valve knob for being in the "Pilot" position.

2.  check pilot adjustment for being full open (counterclockwise 

to open).

3.  If gas is available in the supply tubing, the pilot orifice and/or 

pilot burner is probably restricted by a spider web. Clean pilot 

assembly and relight.

If Pilot Does Not remain on After releasing Knob: 

1.  Follow instructions and hold button down longer and harder.

2.  Determine if pilot flame extends past thermocouple; if not, adjust 

input or clean pilot burner.

3.  Replace thermocouple if millivolts read less than 15 millivolts. 

Main Gas Valve Does not open When Gas Control Is Turned To on:

1.  check for 24 volts to valve by removing one wire and touching 

to the 

SAME TErMINAl 

it was on. Terminal should have a 

light spark. 

Do NoT SHorT AcroSS TErMINAlS, AS IT 

WIll BurN ouT THE GAS coNTrol.

2.  To check for line voltage to furnace, remove front panel and 

short across two-terminal fan control to allow fan to operate 

(Figure 14).

cAuTIoN:

 Label all wires prior to disconnection when servicing 

controls. Wiring errors can cause improper and dangerous 

operation. Verify proper operation after servicing.

IP-Model Pilot

This heater is using a Honeywell "Smart Valve" system for intermittent 

pilot ignition.
On a call for heat by the control turns on a 24 volt mini hot surface 

ignitor which lights a pilot that in turn lights the main burner. The gas 

valve used in this system is a step opening which opens at a lower 

pressure for ignition and then steps to a full inlet pressure of 4" H

2

pressure on Natural Gas and 10" h

2

0 pressure on Propane Gas.

Pilot Flame Adjustment

The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the 

tip of the flame rod. See Figure 10.
To adjust:

1.  Remove the pilot adjustment cover screw.

2.  Turn the inner adjustment screw clockwise 

to decrease 

or counterclockwise 

 

to increase pilot flame. Pilot ad-

justment is shipped at full flow rate. Turn the inner adjustment 

screw clockwise

 if the inlet pressure is too high.

3. Replace the cover screw after the adjustment to prevent gas 

leakage.

ON

OFF

IGNITOR

CONTROL

INLET PRESSURE TAP

OUTLET PRESSURE TAP

PILOT ADJUSTMENT-
UNDER CAP SCREW

PILOT OUTLET

PRESSURE REGULATOR
ADJUSTMENT-UNDER CAP
SCREW

GAS FLOW

IGNITOR

CONTROL

TO 24 V. THERMOSTAT

TO 24 V. COMMON ON TRANSFORMER

TO 24 V."HOT" ON TRANSFORMER

WIRING

I P-MODEL GAS VALVE AND WIRING

IGNITOR-PILOT ASSY.

FAN
SWITCH

MOTOR

HONEYWELL IP
SMART VALVE

120 VAC

LIMIT
CONTROL

VENT SAFETY
LIMIT

THERMOSTAT

40 VA TRANSFORMER

24 VAC

120VAC

VALVE CONTROL
CONNECTOR

L1 "HOT"

L2 NEUTRAL

LADDER WIRING DIAGRAM-IP VALVE

Figure 15

Summary of Contents for FAW40IPXLP-1

Page 1: ...operty damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try t...

Page 2: ...d Tile If this appliance is installed directly on carpeting tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full wid...

Page 3: ...inal venting system may no longer be sized to properly vent the attached appliances Instructions shall also indicate effects of an improperly sized venting system formation of condensate leakage spill...

Page 4: ...can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity Propane Gas may stratify in a cl...

Page 5: ...n in a Confined Space A confined space is an area with volume less than 50 cubic feet per 1 000 Btuh of the combined input rates of all appliances drawing combustion air from that space Small areas su...

Page 6: ...in a horizontal distance of 10 feet 3m 2 This furnace must not be connected to a chimney flue serving a separate solid fuel burning appliance 3 UninsulatedSingle WallMetalPipeshallnotbeusedoutdoors in...

Page 7: ...ide outlet wall plate over outer boot pass the outer boot through the wall and attach side wall plate to furnace side of wall with 2 10 x 1 1 2 38mm provided screws 5 Attach outer boot to the cabinet...

Page 8: ...ehind the furnace Attach furnace to wall at the outer casing top with 2 toggle bolts provided and to floor at the outer casing bottom with 2 10 x 1 1 2 38mm screws provided Gas Supply Check all local...

Page 9: ...cover screw on the control valve Figure 9 and turn the adjustment screw clockwise to reduce flame Replace pilot cover screw to eliminate gas leakage Propane Gas will not require adjustment After use...

Page 10: ...located on the draft diverter 3 Replace front panel If the manual reset vent safety switch continues to shut off the gas flow to the main burners a qualified service person must be contacted to inspe...

Page 11: ...he same terminal it was on Terminal should have a light spark Do not short across terminals as it will burn out the GAS CONTROL 2 To check for line voltage to furnace remove front panel and short acro...

Page 12: ...rn off all electric power to the appliance 3 Remove control access panel front panel 4 Turn gas control knob clockwise to OFF GAS CONTROL SHOWN IN OFF POSITION 5 Wait ten 10 minutes to clear out any g...

Page 13: ...iance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor What To Do If You Smell Gas Do not try to light any appliance Do not touch any e...

Page 14: ...ition OFF Wait for Flame Signal to Disappear Pilot Valve Closes Ignition OFF Main Pilot Valves Close Flame Lost More Than 5 Times in One Call for Heat 5 Minute Retry Delay 3 Second Flame Recycle Delay...

Page 15: ...Flowing Wait to Assure Pilot Gas Tubing is Purged Measure Voltage Between 24V Hot and 24V Common Leads to SmartValve Control Must Measure at Least 19 5 VAC with Igniter Powered See Inset A to Identif...

Page 16: ...31 P8851 ORIFICE Natural 3 REQUIRED 31 P8860 ORIFICE Propane 3 REQUIRED 32 DV1236 MANIFOLD 33 DV1258 CASING FRONT 34 P112 MANIFOLD UNION 35 R1109 BUSHING 3 8 x 1 2 35 R9502 BUSHING 3 8 x 3 4 NATURAL I...

Page 17: ...37134 4 0319 Page 17...

Page 18: ...ase and can be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Mode...

Page 19: ...le cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might result from t...

Page 20: ...ww empirecomfort com Empire Comfort Systems Inc Belleville IL If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question plea...

Reviews: