EMPYRE PRO SERIES INSTALLATION AND OPERATION MANUAL • 2009
INSTALLATION
Trench for Underground Pipes
1. The water
lines must
be properly
insulated
to minimize
heat loss. Ask
your dealer
for the right
underground
water line
insulation.
2. Dig a trench, minimum 24 in (61 cm) deep* and
12 in (30 cm) wide, and make as level as
possible to avoid damage to the tubing.
* Trench should be at least 36 in (91 cm) deep under
driveways.
3. The water lines should be a minimum of 1 in
(2.54 cm) inside dimensions*, rated and
approved for use with high temperature water
and anti-freeze.
*Size of water lines depends on distance; consult with
a qualified heating professional to determine the line
size necessary to meet the demands of your specific
application.
4. Identify each water line clearly in order to
correctly locate the supply and return lines.
5. Lay down 14-2 underground wire approved for
underground installation. Obtain the required
electrical permit and confirm local electrical
code requirements prior to installation.
House
Shop
Insulated Lines
Typical Installation
Water Lines
Foundation Dimensions
The specifications below provide a stable
concrete pad for the Empyre Pro Series furnace.
The open area indicated by ‘E’ in the drawing
provides a channel for plumbing and electrical
conduit.
Pro Series 100
Pro Series 200
Pro Series 400
in
cm
in
cm
in
cm
A
4
10
4
10
5
13
B
36
91
48
122
49
124
C
57
145
67
170
76
193
D
4
10
4
10
4
10
E
8
20
10
25
10
25
F
12
30
25
64
25
64