7 Power Device 

When fitting / replacing batteries; observe correct polarity, 

using only specified batteries. 

Connect the power jumper across the PIN header.

8 Configuration

Once powered, reassemble the device.

The device’s loop address is configured within the menu structure 

of the Radio Hub. 

Refer to the programming manual (Doc Ref: MK98) for full 

programming information. 

Free to download from 

www.emsgroup.co.uk

OUTPUT  2

OUTPUT  1

3VDC SET RST

INPUT 1 INPUT 2 

LED

ENABLE

PO

WER

INPUT 

1

INPUT 

2

FA ULT

CLOSED

0

1

1

64

F-SAFE

N/O COM N/C

IP-    IP+ IP-    IP+

3VDC SET RST

N/O COM N/C

EXPAN1

EXPAN2

RELA

Y ON

RELA

Y ON

2

4

8

16

32

device

unpowered

(pins unlinked)

device

powered

(both pins linked) 

9 LED Operation

The device has six indication LEDs. Pressing the LED enable button 

enables their illumination for 10 minutes before automatically 

timing out.

2x Input Fault: YELLOW LED ON        = FAULT

2x Input Closed: RED LED ON        = ACTIVE

2x Output: RED LED ON        = ACTIVE

CLOSED

FAULT

INPUT 1

INPUT 2

Input 2 

LEDs

Input 1 

LEDs

Output 1 LED Output 2 LED

Operating

Temperature   

-10°C to 55°C

Storage

Temperature   

5°C to 30°C

Humidity   Up to 95% non-condensing

Supply  

 

6x AA Alkaline (Panasonic LR6AD Powerline / Varta  

   4006 

Industrial)

  

CAUTION! 

Fitting of an incorrect battery type invalidates the product certification and 

may result in poor performance.

Output rating   

2A @ 24Vdc

IP Rating 

 

IP65

Operating Frequency 868MHz

Output Transmitter

Power   

 

Auto adjusting 0 - 14 dBm (0 - 25 mW) 

Dimensions 

 

270mm (W) 205mm (H) 75mm (D)

Weight 

  0.95kg

Location 

 

Type A: For indoor use

2012/19/EU (WEEE directive):

Products marked with this symbol cannot be 

disposed of as unsorted municipal waste in the 

European Union. For recycling, return this product to 

your local supplier upon purchase of equivalent new 

equipment, or dispose of it at designated collection 

points. For more information see 

www.recyclethis.info

Dispose of your batteries in an environmentally 

friendly manner according to your local regulations.

European Union 

directives

EMS Security Group Ltd hereby declares that this 

device is in compliance with the essential 

requirements and other relevant provisions of 

Directive 2014/53/EU (R&TTE directive).

Approved to

EN54-18:2005. Fire detection and fire alarm 

systems. Part 18: Input/output devices.

EN54-25:2008. Incorporating corrigenda 

September 2010 and March 2012. Fire detection 

and fire alarm systems. Part 25: Components using 

radio links.

Certification

     

Certification body  

CPR Certificate DOP  0359-CPR-0039 

EMS Security Group Ltd. Technology House, Herne 

Bay, Kent, CT6 8JZ, United Kingdom

Manufacturer

Year of 

manufacture   

See devices serial number label 

          

0359

10

Specification

Regulatory Information