To install CellSPY Lite, place the black clamp
over the negative post and the red over the
positive.
Clamp the WCT over the intercell cable with
arrow pointing in direction of charge current,
or towards the most negative cell in the string.
Open the application on the provided mobile
device- at the bottom of the home page, make
sure all cells are responding.
To power the WCT, power it over 8-60V.
Check the voltage across the batteries with a
voltmeter to double check.
Install the remaining CellSPY Lite sensors in
order. If you are using multiple boxes, start
with sensor 1 from box 2 after installing all
sensors from box 1.
Ensure that the thermistor, is as close to the
post as possible.