DEVICE CONFIGURATION
116
smart Econ - emz-HCW - 180116
Configure solid fuel boiler
(Only for systems with solid fuel boiler)
• Select ›SOLID FUEL BOILER‹ in the ›COMMISSIONING‹ menu.
• Change the name of this solid fuel boiler if necessary.
• Change other parameters if necessary.
- ›start-up temperature‹: Minimum boiler flow temperature for release of charge pump
(setting range 0-99 °C)
- ›hysteresis (K)‹: Minimum temperature difference required between boiler and buffer to start the
charge pump (start-up hysteresis)
Start of buffer charging, both conditions must be met:
1.)The boiler temperature has reached the start-up temperature and
2) the boiler temperature is higher by the hysteresis than the current temperature in the buffer.
SOLID FUEL BOILER
^
NAME
Solid Fuel Boiler
start-up temperature
55
hysteresis (K)
5