DEVICE CONFIGURATION
136
smart Econ - emz-HCW - 180116
Setting the domestic hot water setpoint temperature (Installer)
• Select ›SETTINGS‹ in the ›DOMESTIC HOT WATER‹ menu.
• Change the ›desired value‹ or the ›hysteresis‹ if necessary.
The pump is switched on as soon as the domestic hot water sensor value falls below the setpoint
by the hysteresis.
It is switched off as soon as the setpoint is reached.
“Change values” on page 23
• Activate or deactivate ›legionellae‹.
If the function is activated with ›legionellae‹ ›YES‹ (default), the thermal disinfection program is
carried out once a week every Monday.The domestic hot water is heated to 63°C to kill germs.
SETTINGS
^
desired value
50
hysteresis (K)
5
legionellae
YES
BACK
i