SETTINGS DURING OPERATION
28
smart Econ - emz-HCW - 180116
Operating mode ›AUTOMATIC‹
System control according to the time programs entered and the chosen ambient temperature set-
points (“›HEAT CIRCUITS‹ menu” on page 36).
The user can make changes with the smart Econ room controller's setting wheel, see “Operating the
smart Econ room controller” on page 16.
As this is set directly at the smart Econ room controller, each user can control the entire heating sys-
tem for the respective area without requiring any special knowledge of the heating installation or its
control system.
Operating mode ›DAY‹
Time programs are not considered.The highest room temperature setpoint entered for the respec-
tive heating circuit is used.
Operating mode ›NIGHT‹
The time programs are not considered, the temperature is always controlled to the room tempera-
ture setpoint entered for setback operation.The temperature is also controlled to this setback room
temperature on individual programmed holidays as well as on the last holiday of a holiday period.
See “›HOLIDAY PERIODS‹ menu” on page 35
Operating mode ›FROST PROTECTION‹
Time programs are not considered.The temperature is always controlled to the frost protection room
temperature.
Except for the last day, the temperature is also set to this value during a holiday period.
See “›HOLIDAY PERIODS‹ menu” on page 35
You can change the frost protection temperature directly in the settings of the ›FROST PROTEC-
TION‹ operating mode and it applies to the entire system.
Operating mode ›SUMMER‹
The space heating is off, all other functions (water heating, solar heating system, etc.) are
active.The heating circuit pumps and mixers are switched on briefly once a week to prevent them
from getting stuck when they are not being used regularly during the summer.
Operating mode ›FLOOR PAVEMENT HEATING‹
Note:
The ›FLOOR PAVEMENT HEATING‹ mode is only available for heating circuits with mixers.
NOTE
With the exception of the operating modes ›FROST PROTEC-
TION‹ and ›OFF‹, no messages are displayed indicating that
the selected operating mode is active.
The selected operating mode is displayed in the footer.
NOTE
The frost protection function is always active in all operating
modes except the ›OFF‹ operating mode.