15
Connection to power supply
The differential temperature controller smart Sol plus is connected to the
power supply via three groups of spring-type terminals which are
visible once the terminal cover is opened.
To introduce the cables, release the screws on the strain relief device;
if necessary, remove the strain relief device.
In case of flush mounting of the cables, the break-out segments in the housing
base can be removed carefully and the cables routed through these ports.
The central terminal block is the interface to a potential-free change-over contact.
The spring-type terminals for the Power, RO1 to RO4 and REL, and for TS1 to TS10
can accommodate solid wires up to a cross section of 1.5 mm
2
.
Appropriate stranded wires must be preassembled with cable end sleeves.
For the strain relief device function, TS1 to TS10 and REL require
cable cross sections of at least 5mm, for Power, RO1 to RO4 at least 7mm.
Danger!
Mortal danger due to electrocution! Whenever work is performed
on the open terminal cover, all poles of the power supply must be
disconnected reliably and protected against being switched on again!
Terminal block
RO1-RO4/Power
Terminal
block REL
Terminal block
TS1-TS10