90
Professional mode
If outputs on the controller are not
assigned, these channels can be
used as thermostats.
Here, the appropriate
channel is selected.
For the heating function,
T ON must be < T OFF.
For the cooling function,
T ON must be > T OFF.
Up to four time slots can be assigned
to each thermostat function.
Define times for activation
and deactivation.
Continue via the menu item
›Output parameter‹.
Perform activation.
Define the start signal.
Depending on the selection of ›Start‹,
the following parameters are shown.
The output has already been defined
by the selection - the related sensor
remains to be defined.
Define switch-ON/OFF temperature.
Continue to scroll.
Thermostat RO3
Thermostat RO4
1.3.1 Thermostat
25.08.2012
10:35
Activation
Start
Sensor
Output
T ON
T OFF
Timer,thermostat
---
RO3
0.0°C
0.0°C
1.3.1 Thermostat RO3
25.08.2012
10:35
t ON 1
t OFF 1
t ON 2
t OFF 2
t ON 3
t OFF 3
t ON 4
00:00
00:00
00:00
00:00
00:00
00:00
00:00
1.3.1 Thermostat RO3
25.08.2012
10:35