91
Professional mode
Here, the general settings for the
assigned outputs are defined.
›t tear-off‹ and ›n tear-off‹ define
how long and at which speed the
pumps are to run on starting.
Select an output...
60
50
40
30
20
10
0
2
4
6
8
10 12 14
Speed
in %
Temperature difference in K
Note!
The ›Speed delta‹ parameter defines the speed change for step control.
Speed is adjusted by each set value by changing the temperature.
Step control is either selected in the ›1.3.5 dT control‹ menu or in the
›1.3.6 Fixed T control‹ menu.
Parameters for the following sample diagram:
n-min = 30% / n-max = 100% / algorithm = dT (menu 1.3.7) /
dT 1 = 2.0K / dT-on 1 = 5.0K / dT-target 1 = 10.0K /
control 1 = stepped (menu 1.3.5) / speed delta = 10% (menu 1.3.7).
Solar pump 1
Solar pump 2
Boiler
Thermostat RO3
Time for tear-off
Speed for tear-off
Speed delta
10s
100%
10%
1.3.7 Output parameter
25.08.2012
10:35