94
Professional mode
Via ›T-min tank 1‹ and
›T-min tank 2‹, specify the
minimum temperature required
for the tank in question.
Select whether the ›Priority tank‹
or the ›Secondary tank‹ are to be
cooled.
Continue via the menu item
›Collector cooling‹.
Here, collector cooling is activated:
once the collector temperature
›T max. Coll. 1‹, or ›T max. Coll. 2‹ is
reached, the appropriate solar circuit
pump continues to operate until the
tank limit temperature is reached.
To protect the pump, the collector
emergency switch-off in solar circuits
with high-efficiency pumps is reduced
to 100°C. Collector cooling is not
possible at higher temperatures!
Return to ›1.3. Basic functions‹.
Continue with ›Commissioning‹.
Here, new commissioning
can be started - e. g. if a new
hydraulic system is to be selected.
=> ›Commissioning mode‹
as of page 61.
Continue with ›Delta T control‹.
Hyst
Soft charge
dT
T min.tank1
T min.tank2
Tank
5.0K
5.0K
45.0°C
45.0°C
Priority tank
1.3.3 Holiday function
25.08.2012
10:35
Activation
T max.Collector 1
121.0°C
1.3.4 Cooling funct.
25.08.2012
10:36
You really want to
start commission.?
No
Yes
0 Welcome
25.08.2012
10:36