95
Professional mode
If control algorithms have been
defined as ›dT‹ under ›1.3.7 Output
parameter‹, the appropriate outputs
can be configured here.
Via ›dT ON‹, the switch-ON
temperature, via ›dT OFF‹, the
switch-OFF temperature and via
›dT targ.‹, the target differential
temperature are set. (Differential
temperature between collector
and tank, bottom).
Continue with ›Fixed T control‹.
If control algorithms have been
defined as ›Fixed T‹ under ›1.3.7
Output parameter‹, the appropriate
outputs can be configured here.
In case of the fixed temperature
control, the collector is controlled to
the preset temperature via a variable
pump delivery rate.
Continue with ›Post Heating Request‹.
Note!
The ›dT targ.1‹ parameter is displayed in the
›1.3.5 dT control‹ menu for systems with 2 collector fields.
With ›dT targ.1‹ the maximum temperature
difference between both collector sensors is specified.
Once this value is exceeded, the pump of the „colder“ collector field
is deactivated in order to increase efficiency.
Activation dT 1
dT 1
dT-ON 1
dT-OFF 1
dT targ.1
Contl 1
2.0K
8.0k
4.0k
10.0K
step-wise
1.3.5 dT control
25.08.2012
10:37
Control 2
Variant 2
T-fixed 2
step-wise
70.0°C
1.3.6 Fixed temp.cont...
25.08.2012
10:37