Professional mode
Here, reheating can be activated.
The boiler is defined as ›Solid-fuel
boiler‹ or ›Gas/oil‹.
In case of solid-fuel boilers reheating
is made via the charge pump of the
drinking water tank and is only
activated if the temperature of the
tank is within the values ›Min. temp.‹
und ›Max. temp.‹.
Use ›Boiler sensor‹ to assign the
temperature sensor which supplies
the temperature value of the boiler.
Up to six time blocks can
be activated for reheating.
›Ref. temp.‹ is used to define the set
temperature at the top tank sensor.
If the temperature falls below ›Ref.
temp.‹ by ›Hysteresis‹, the control
activates the reheating cycle via the
heating boiler until ›Ref. temp.‹ is
reached.
Each period can be defined with
›Weekends‹, Monday - Sunday‹ or
›Monday - Friday‹.
Continue with ›Efficiency functions‹.
Activation
Reference temperature
Starting time
End time
Time period
45.0°C
00:00
23:59
Daily
1.3.10 Post Heating R...
25.08.2012
10:37
Activation
Boiler type
Hysteresis
Minimum temperature
Maximum temperature
Sensor boiler
Solid fuel boiler
10.0K
40.0°C
55.0°C
TS6
1.3.10 Post Heating R...
25.08.2012
10:37
Sensor boiler
Time block 1
Time block 2
Time block 3
Time block 4
Time block 5
Time block 6
TS6
1.3.10 Post Heating R...
25.08.2012
10:37