SETTINGS IN THE PROFESSIONAL MODE
smart Stove - 0142 - 42WMSUGAT2-C
57
The menu is only available for systems with charge zone valve
(systems 2, 3, 7).
Select ›Charge zone v‹.
The ›Inverted‹ function inverts the switching function of the
valve, e.g. if valve installation does not comply with the
standard.
The controller will then exchange energized and de-energized
conditions.
Return to ›1.3 Basic functions‹.
Select ›Commissioning‹.
Here, new commissioning can be started - e. g. if the hydraulic
system has been changed.
Select ›Yes‹ to start commissioning.
“Commissioning” on page 50
Return to ›1.3 Basic functions‹.
Select ›Control parameters‹.
The menu depends on the selected hydraulic system.
System 1:
›Add. heat enabled‹: Recharging of the tank by the additional
heating can be disabled or enabled (if available)
›Charge start‹: Minimum stove temperature for starting the
loading pump
›Charge offset‹: Temperature offset for starting the
speed control of the loading pump
›DPD‹: Dynamic pump delay, see page 24
1.3.7 Outputs
17.03.2016
13:34
Charge zone v
1.3.7 Outputs
17.03.2016
13:34
Inverted
0 Welcome
17.03.2016
13:34
You really want to
start commission.?
No
Yes
1.3.14 Control para.
17.03.2016
10:44
Add. heat enabled
Charge start
58°C
Charge offset
5K
DPD
0min*K