SETTINGS IN THE PROFESSIONAL MODE
64
smart Stove - 0142 - 42WMSUGAT2-C
Monitoring
Here, the limits for overtemperature protection can be
changed.
›TS1 Limit‹: Limit for overload of fuel in stove
›TS2 Limit‹ to ›TS4 Limit‹: Limits for tank temperature too high
›TS5 Limit‹: Limits for hot-water tank temperature too high
(hydraulic systems 3 and 7 only)
Return to ›Main menu‹.
Select ›Monitoring‹.
Under ›1.6 Monitoring‹, the following items are additionally
available next to the operation mode menus:
- ›Pump monitoring‹
- ›Sensor balancing‹
Select ›Pump monitoring‹.
When activated, ›Pump monitoring‹ observes the temperature
change during the ›Monitoring time‹.
If the temperature does not change during this time, the con-
troller releases an alarm.
Continue with ›Sensor balancing‹.
Long piping and other factors may distort measured variables.
Here, an offset value can be entered for each sensor.
Return to ›Main menu‹.
Select ›Login‹.
17.03.2016
13:34
TS1 Limit
85°C
TS2 Limit
85°C
TS3 Limit
85°C
TS4 Limit
75°C
TS5 Limit
75°C
1.3.12 Limits
1.6 Monitoring
17.03.2016
14:04
Error list
Pump monitoring
Sensor balancing
1.6.6 Pump monito...
17.03.2016
14:04
Activation
Temp. change 1
0.5K
Temp. change 2
0.5K
Monitoring time
15min
1.6.5 Sensor balan...
17.03.2016
14:04
TS1 Offset
0.0°C
TS2 Offset
0.0°C
TS3 Offset
0.0°C
TS4 Offset
0.0°C
TS5 Offset
0.0°C