EN-KO Electronic Control Systems
AMF 4.0/ENG/K.K./02
21
SPECIFICATIONS
Power Supply
9-35 VDC
140 mA (all relays are de-energized)
Ambient
Temperature
-10
°
C / +70
°
C
Relative Humidity
%10-%95 non-condensing
Relay outputs
For cranking, fuel solenoid, preheating and auxiliary outputs max.
12V/24VDC 6 A, For mains and generator contactor relays max.
250VAC/10 A
Voltage measurement
20-300VAC
Frequency
measurement
1-99 Hz
Current
measurements
.../5 A current inputs (current transformer should be used)
Connection
Screw socket
Measurement
Accuracy
Phase voltages
: + / - %2
Frequency
: + / - 0.1Hz
Phase currents
: + / - %2
Charge Excitation
Current
80mA @ 12VDC
160mA@ 24VDC
Housing
PPO (Polyphenylene oxide) %30 Glass Fiber
Protection Class
IP 52 (Front side)
Weight
600 gr. (aprox.)
Dimensions (WxHxD)
192x144x62 mm
Panel Cut Out
186x138 mm
Mounting Installation
Front panel mounted with metal screw fixings
DIMENSIONS AND MOUTING