Note1)
Do not Run/Stop operation by switching on/off electromagnetic
contactors (Mc0, Mc1) on the primary or secondary sides of the
inverter.
Operate the inverter by Run/Stop commanding [FW/RV].
L
Power
supply
Mc0
L1, L2
Mc1
FW(RV)
ON,OFF
ON,OFF
ON,OFF
ON,OFF
ON,OFF
Inverter
Motor
Note 2)
Motor Terminal Surge Voltage Suppression Filter
In a system using an inverter with the voltage control PWM system, a
voltage surge caused by the cable constants such as the cable length
(especially when the distance between the motor and inverter is 10m or
more) and cabling method may occur at the motor terminals.
Note 3)
Input power disconnection
This inverter is not able to protect input power disconnection.
Be careful to connect the wires.