EDT 1323
CONTROL PARAMETERS TABLE
RDI
Switch hysteresis for compressor.
1
20
°C
2
RLL
The lower limit of the setpoint of the cold room.
-55
Rul
°C
-50
Rul
The upper limit of the setpoint of the cold room.(+100°C for NTC, +150°C for PTC.)
Rll
150
°C
150
Rof
The offset value for the refrigeration.
-20
20
°C
0
Cpo
Delay time for the compressor after power is on
0
15
min
0
Csb
Delay time required between successive restarts of the compressor.
0
15
min
5
Cfs
Delay time required for the compressor to restart following a stop.
0
15
min
3
Cdp
Compressor protection delay (
n
= no delay,
y
= 3s delay)
N
Y
N
Cpp
Compressor protection during temperature sensor is broken (
off
= Compressor is Off during
sensor failure,
on
= Compressor is On during sensor failure)
off
on
Off
Dty
Defrosting type (
El
=Electrical defrost,
I
n
= hot gas defrost )
Dit
Defrosting interval
Dtl
Defrosting time limit
Dst
Defrosting temperature. If evaporator temperature is higher than this value, defrosting is disabled.
Dpo
Defrosting after power on (
y
=Defrosting begins when power is on,
n
=Defrosting doesn’t begin when power is on)
Ddp
Delay time for defrosting after power is on
Ddl
Locking of temperature indication during defrosting. (
n
= temperature is displayed during defrosting,
y
= Displayed value do not changes during Defrosting process.)
Ddt
Drainage time
Daa
Time interval required for alarm activation after completing defrosting
Ddc
Compressor with delay time at the selection of hot gas defrosting (
y
= Yes,
n
= No,
Note: Delay time is adjusted by using
CPO
,
CSB
and
CFS
parameters)
Dpr
The display of evaporator temperature
Dtb
Defrosting period time base (
hr
= Hour, minute
Sc
=Minute,second)
Adi
Switch hysteresis for alarm
Alr
Limit for low alarm level (If temperature falls down setpoint by this value, buzzer starts ringing)
Ahr
Limit for upper alarm level (If temperature exceeds setpoint by this value, buzzer starts ringing)
Apd
Time delay required for alarm to become active after power is on
Frt
Fan is controlled depending on temperature.
Fst
If evaporator temperature is above this parameter, fan stops
Fdi
Switch hysteresis for fan
Fco
Does fan stop when compressor stops? (
off
= Yes,
on
= No)
Fdo
Does fan stop during defrosting? (
off
= Yes,
on
= No)
Fdt
The time period of stopping fan after drainage.
el
in
el
0
99
Hour/(min)
8
1
99
Min./(sec.)
30
-55
99
°C
2
N
Y
Y
0
15
min./(sec.)
2
0
15
Hour
2
N
Y
Y
°C
hr
Sc
hr
0
15
°C
2
1
50
°C
10
1
50
°C
10
0
15
Hour
2
N
Y
Y
-55
99
1
°C
2
15
°C
2
off
On
off
off
On
off
0
15
min./(sec.)
2
N
Y
N
0
31
min
0
N
Y
N
Does the fan control depend on the temperature of cold room? (
Y
= Yes,
n
= No)
If (
n
) is selected,
while
(
y
) is selected, fan stops while the difference between cold room and the evaporator temperature
is lower than the value of the
parameter
fan stops
evaporator temperature is above the value of
Fst
parameter,
If
Fst
.
Fan restarts again, if the difference between cold room and the evaporator temperature
becomes higher than the total of the values of
fst
and
fdi
parameters.
Fac
Min.
Max.
Unit
Initial
values
Refrigeration control parameters
Compressor protection parameters
Defrost control parameters
Alarm parameters
Fan control parameters
3/3
EDT1323
-E-04
100
100