background image

 

EDT 1323

 CONTROL PARAMETERS TABLE

RDI

Switch hysteresis for compressor.

1

20

°C

2

RLL

The lower limit of the setpoint of the cold room.

-55

Rul

°C

-50

Rul

The upper limit of the setpoint of the cold room.(+100°C for NTC, +150°C for PTC.)

Rll

150

°C

150

Rof

The offset value for the refrigeration.

-20

20

°C

0

Cpo

Delay time for the compressor after power is on

0

15

min

0

Csb

Delay time required between successive restarts of the compressor.

0

15

min

5

Cfs

Delay time required for the compressor to restart following a stop.

0

15

min

3

Cdp

Compressor protection delay (

n

= no delay, 

y

= 3s delay)

N

Y

N

Cpp

Compressor protection during temperature sensor is broken (

off

 = Compressor is Off during 

sensor failure,   

on

=  Compressor is On during sensor failure)

off

on

Off

Dty

Defrosting type (

El

=Electrical defrost, 

I

n

=  hot gas defrost )

Dit

Defrosting interval

Dtl

Defrosting time limit

Dst

Defrosting temperature. If evaporator temperature is higher than this value, defrosting is disabled.

Dpo

Defrosting after power on (

y

=Defrosting begins when power is on, 

                                          

n

=Defrosting doesn’t begin when power is on)

Ddp

Delay time for defrosting after power is on

Ddl

Locking of temperature indication during defrosting. (

n

= temperature is displayed during defrosting,

 

y

= Displayed value do not changes during Defrosting process.)

Ddt

Drainage time

Daa

Time interval required for alarm activation after completing defrosting 

Ddc

Compressor with delay time at the selection of hot gas defrosting (

y

= Yes, 

n

= No, 

Note: Delay time is adjusted by using 

CPO

CSB

 

and

 

CFS

 

parameters)

Dpr

The display of evaporator temperature

Dtb

Defrosting period time base (

hr

= Hour, minute  

Sc

=Minute,second) 

Adi

Switch hysteresis for alarm

Alr

Limit for low alarm level (If temperature falls down setpoint by this value, buzzer starts ringing)

Ahr

Limit for upper alarm level (If temperature exceeds setpoint by this value, buzzer starts ringing)

Apd

Time delay required for alarm to become active after power is on

Frt

Fan is controlled depending on temperature. 

Fst

If evaporator temperature is above this parameter, fan stops

Fdi

Switch hysteresis for fan 

Fco

Does fan stop when compressor stops? (

off

= Yes, 

on

= No)

Fdo

Does fan stop during defrosting? (

off

= Yes, 

on

= No)

Fdt

The time period of stopping fan after drainage.

el

in

el

0

99

Hour/(min)

8

1

99

Min./(sec.)

30

-55

99

°C

2

N

Y

Y

0

15

min./(sec.)

2

0

15

Hour

2

N

Y

Y

°C

hr

Sc

hr

0

15

°C

2

1

50

°C

10

1

50

°C

10

0

15

Hour

2

N

Y

Y

-55

99

1

°C

2

15

°C

2

off

On

off

off

On

off

0

15

min./(sec.)

2

N

Y

N

0

31

min

0

N

Y

N

Does the fan control depend on the temperature of cold room? (

Y

= Yes, 

n

= No)

If (

n

) is selected, 

while 

(

y

) is selected, fan stops while the difference between cold room and the evaporator temperature

is lower than the value of the 

 parameter

fan stops 

evaporator temperature is above the value of 

Fst

 parameter, 

If 

Fst

.

Fan restarts again, if the difference between cold room and the evaporator temperature
becomes higher than the total of the values of 

fst

 and 

fdi

 parameters.

Fac

Min.

Max.

Unit

Initial
values

Refrigeration control parameters

Compressor protection parameters

Defrost control parameters

Alarm parameters

Fan control parameters

3/3

EDT1323

-E-04

100

100

Reviews: