ASP station 2000
6 Commissioning
Hauser
83
Several programme combinations are available for the 7 programme version:
Main programmes
Four main programmes are available. Select a main programme from the item PROG.
NAME. (see “Creating a main programme” on page 84.)
Switching programmes
Two programme pairs (1
⇔
U1 and 2
⇔
U2) are available. The switching programmes (U1
and U2) are permanently assigned to the main programmes (1 and 2). You can trigger
a switch from the main programme to the switching programme as follows.
You can define separate sampling programmes and bottles for the switching
programmes.
Event programme
The event programme is activated by a digital input.
!
Note!
For this function, one of the digital inputs must be assigned and configured using the
<EVENT> function.
You can define a separate sampling programme and separate bottles for the event
programme.
1
A main programme is active.
2
A main programme and a switching programme are active.
1+Event
A main programme and the event programme are active.
2+Event
A main programme, a switching programme and the event programme are
active.
Day
Switch to the switching programme at two settable times in one day.
Week
Switch to the switching programme on three settable days in the week.
Q greater
Switch to switching programme on exceeding a settable threshold value.
!
Note!
An analogue signal must be connected to the analogue input of the sampler
for this function.
Q smaller
Switch to switching programme on undershooting a settable threshold value.
Ext. signal
Switch to switching programme by means of an external digital signal.
!
Note!
For this function, one of the digital inputs must be assigned and configured
using the <SWITCH> function.