5.4.2
Level measurement
• Always install the device below the lowest measuring point.
• Do not install the device at the following positions:
– In the filling curtain
– In the tank outlet
– In the suction area of a pump
– Or at a point in the tank which could be affected by pressure pulses from the agitator.
A0024405
5.5
Mounting of the profile seal for universal process
mounting adapter
For details on mounting, see KA00096F/00/A3.
5.6
Post-installation check
Is the device undamaged (visual inspection)?
Does the device comply with the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature range
• Measuring range
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected against precipitation and direct sunlight?
Are the securing screws tightened securely?
Is the pressure compensation element pointing downwards at an angle or to the side?
To prevent moisture from penetrating, ensure that the connecting cables/plugs are pointing downwards.