Cerabar PMP23 IO-Link
System integration
Hauser
21
8.2.1
Hauser-specific device data
Designation
ISDU
(dec)
ISDU
(hex)
Size
(byte)
Data
type
Access Default
value
Value range
Offset /
Gradient
Data
storage
Range
limits
Extended Ordercode
259
0x0103
60
String
ro
ENP_VERSION
257
0x0101
16
String
ro
36587
Simulation switch output
(OU1)
85
0x0055
1
unit
r/w
0 ~ off
1 ~ low
2 ~ high
No
Simulation current output
(OU2)
66
0x0042
1
unit
r/w
0 ~ off
4 ~ 4 mA
5 ~ 8 mA
6 ~ 12 mA
7 ~16 mA
8 ~ 20 mA
9 ~ 21.95 mA
otherwise 3.5 mA
No
Unit changeover (UNI)
67
0x0043
1
unit
r/w
0 ~ bar
1 ~ kPa
2 ~ MPa
3 ~ psi
Yes
Zero point configuration
(ZRO)
68
0x0044
4
int
r/w
0
as 00.00%
Default 0.00%
Yes
Zero point adoption (GTZ) 69
0x0045
1
unit
w
No
Damping (TAU)
70
0x0046
2
unit
r/w
20
in 000.0 sec
Default 2.0 sec
0.1
Yes
Value for 4 mA (STL)
71
0x0047
4
int
r/w
0
as 00.00%
Default 0.00%
bar: 0 / 0.001
kPa: 0 / 0.1
MPa: 0 /
0.0001
psi: 0 / 0.01
Yes
Value for 20 mA (STU)
72
0x0048
4
int
r/w
10000
as 00.00%
Default 100.00%
bar: 0 / 0.001
kPa: 0 / 0.1
MPa: 0 /
0.0001
psi: 0 / 0.01
Yes
Pressure applied for 4mA
(GTL)
73
0x0049
1
unit
w
No
Pressure applied for
20mA (GTU)
74
0x004A
1
unit
w
No
Alarm current (FCU)
75
0x004B
1
unit
r/w
MAX
0 ~ MIN
1 ~ MAX
Yes
Current output (I)
76
0x004C
1
unit
r/w
ON
0 ~ ON
1 ~ OFF
Yes
Switch point value /
Upper value for pressure
window, output 1 (SP1 /
FH1)
77
0x004D
4
int
r/w
9000
as 00.00%
Default 90%
bar: 0 / 0.001
kPa: 0 / 0.1
MPa: 0 /
0.0001
psi: 0 / 0.01
Yes
Switchback point value /
Lower value for pressure
window, output 1 (rP1 /
FL1)
78
0x004E
4
int
r/w
1000
as 00.00%
Default 10%
bar: 0 / 0.001
kPa: 0 / 0.1
MPa: 0 /
0.0001
psi: 0 / 0.01
Yes
Switching delay time,
Output 1 (dS1)
79
0x004F
2
unit
r/w
0
in 00.00 sec
0 / 0.01
Yes
Switchback delay time,
Output 1 (dR1)
80
0x0050
2
unit
r/w
0
in 00.00 sec
0 / 0.01
Yes