Technical data
Cerabar PMP23 IO-Link
66
Hauser
16.5 Process
16.5.1 Process temperature range for devices with metallic process
isolating diaphragm
Device
Process temperature range
PMP23
–10 to +100 °C (+14 to +212 °F)
PMP23
Sterilization in place (SIP)
At +135°C (+275 °F) for a maximum of one hour (device in operation but not within
measuring specification)
Applications with changes in temperature
Frequent extreme changes in temperatures can temporarily cause measuring errors.
Internal temperature compensation is faster the smaller the change in temperature and
the longer the time interval.
For further information please contact your local Hauser Sales Center.
16.5.2 Pressure specifications
L
WARNING
The maximum pressure for the measuring device depends on the lowest-rated
element with regard to pressure.
‣
For pressure specifications, see the "Measuring range" section and "Mechanical
construction" section in the Technical Information.
‣
The Pressure Equipment Directive (2014/68/EU) uses the abbreviation "PS". The
abbreviation "PS" corresponds to the MWP (maximum working pressure) of the
measuring device.
‣
MWP (maximum working pressure): The MWP (maximum working pressure) is
specified on the nameplate. This value is based on a reference temperature of
+20 °C (+68 °F) and may be applied to the device for an unlimited period of time.
Observe the temperature dependency of the MWP.
‣
OPL (over pressure limit): The test pressure corresponds to the over pressure limit of
the sensor and may only be applied temporarily to ensure that the measurement is
within the specifications and no permanent damage develops. In the case of sensor
range and process connections where the over pressure limit (OPL) of the process
connection is smaller than the nominal value of the sensor, the device is set at the
factory, at the very maximum, to the OPL value of the process connection. If you want
to use the entire sensor range, select a process connection with a higher OPL value.