Ecograph T, RSG35
Appendix
Hauser
107
Navigation
Expert → Inputs → Universal inputs → Universal input x → Meas. val. corrct → Actual
value
Direct access code: 220056-0xx
Examples: Universal input 1: 220056-000; Universal input 12: 220056-011
Description
Enter the upper value actually measured here (e.g. measuring range 0°C to 100°C:
measured value 100.5°C).
Only visible if signal = current or voltage.
User entry
Number (max. 8 digits)
Factory setting
100
"Totalization" submenu
Navigation
Expert → Inputs → Universal inputs → Universal input x → Totalization
Description
Set up only required for totalization of flow or power consumption.
Totalization
Navigation
Expert → Inputs → Universal inputs → Universal input x → Totalization →
Totalization
Direct access code: 220030-0xx
Examples: Universal input 1: 220030-000; Universal input 12: 220030-011
Description
By totalizing the analog signal (e.g. flow rate in m³/h) quantities (in m³) can be calculated.
Options
No, Yes
Factory setting
No
Totalization base
Navigation
Expert → Inputs → Universal inputs → Universal input x → Totalization →
Totalization base
Direct access code: 220031-0xx
Examples: Universal input 1: 220031-000; Universal input 12: 220031-011
Description
Select the required time base. Example: ml/s -> time base seconds (s); m³/h -> time base
hours (h).
Only visible if totalization = yes.
Options
Second (s), Minute (min), Hour (h), Day (d)
Factory setting
Second (s)