Appendix
Ecograph T, RSG35
110
Hauser
Navigation
Expert → Inputs → Universal inputs → Universal input x → Fault mode → Cable open
circ.
Direct access code: 220060-0xx
Examples: Universal input 1: 220060-000; Universal input 12: 220060-011
Description
Cable open circuit detection
Only visible if signal = "Voltage" and range = "1-5 V" or "1-5 V squared".
Options
Off, On
Factory setting
On
Lower error value
Navigation
Expert → Inputs → Universal inputs → Universal input x → Fault mode → Lower error
value
Direct access code: 220065-0xx
Examples: Universal input 1: 220065-000; Universal input 12: 220065-011
Description
When NE43 is switched off, defines the value that must be undershot for the device to
output an error.
Only visible if signal = "Current", range = "4-20 mA", and NAMUR NE 43 = "Off".
User entry
Number (max. 8 digits); 0 to 4 mA
Factory setting
3.9mA
Upper error value
Navigation
Expert → Inputs → Universal inputs → Universal input x → Fault mode → Upper error
value
Direct access code: 220066-0xx
Examples: Universal input 1: 220066-000; Universal input 12: 220066-011
Description
When NE43 is switched off, defines the value that must be exceeded for the device to
output an error.
Only visible if signal = "Current", range = "4-20 mA", and NAMUR NE 43 = "Off".
User entry
Number (max. 8 digits); 20 to 22mA
Factory setting
20.8mA