Appendix
Ecograph T, RSG35
116
Hauser
Navigation
Expert → Inputs → Digital inputs → Digital input x → Action
Direct access code: 250003-00x
Examples: Digital input 1: 250003-000; Digital input 6: 250003-005
Description
Set up the function of the control input.
Only visible if function = control input.
Action
Description
Start/stop recording
The device only saves data as long as a high signal is present.
Screensaver on
Switches backlight/display off, low = off, high = on.
Lock setup
The user can only change the setup if a low signal is present.
Time synchronization
If a high signal is applied, the device rounds the system time up or down (only for
low→high change) to the nearest minute: 0 to 29 → Round down; 30 to 59 →
round up.
Set point monitoring
on/off
The entire set point monitoring function of the device can be switched on (for
"high") or switched off (for "low").
Block keyboard/navigator The device can only be operated if a low signal is present. Otherwise all key
activation and navigator actions are discarded.
Start/stop analysis 1
Starts/ends the external analysis (the analysis only runs as long as the signal is
high). Measured value acquisition for the graphic display continues.
Options
Switched off, Start/stop recording, Screensaver on, Block set up, Time synchronization, Set
point monitoring on/off, Block keyboard/navigator, Start/stop analysis 1
Factory setting
Switched off
Switches relay
Navigation
Expert → Inputs → Digital inputs → Digital input x → Switches relay
Direct access code: 250006-00x
Examples: Digital input 1: 250006-000; Digital input 6: 250006-005
Description
Switches the respective relay when the digital input is low or high. Please take note of the
connection hints in the Operating Instructions!
Only visible if function = control input, on/off event, event+operation time.
Options
Not used, Relay x
All the available relays are displayed
Factory setting
Not used
Description 'H'
Navigation
Expert → Inputs → Digital inputs → Digital input x → Description 'H'
Direct access code: 250007-00x
Examples: Digital input 1: 250007-000; Digital input 6: 250007-005